Symptom
A motor, valve, light, or solenoid does not operate when the program calls for it. The output may show on in the software, on the module indicator, or neither.
The short answer
Outputs Not Energizing
Between the bit in the program and the load in the field there is a chain: the logic, the output image, the module, the module fuse and field power, the wiring, the interposing relay, and the load itself. Find where the chain breaks by working from the panel outward: is the rung true, is the output bit on, is the module indicator lit, is there voltage at the module terminal, is there voltage at the relay coil and at the load. The break is between the last good measurement and the first bad one.
Key points
- Confirm the rung is actually true and the output bit is on before touching hardware; a false rung is the most common cause.
- The module indicator lit with no voltage at the terminal means a blown module fuse or no field power to that common.
- Voltage at the module terminal and none at the load means wiring or the interposing relay.
- A forced output, or the processor in program mode, overrides the logic and looks like a failure.
- A remote rack with a lost connection holds its outputs at their fault state no matter what the program says.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| The rung is not true | Look at the rung online. A permissive, an interlock, or a mode selector that is not satisfied is the usual reason. The output bit is off, and the module is doing what it was told. |
| Output forced off, or a force table active | The software shows forces installed. A force left from commissioning holds the output regardless of logic. |
| Processor not in run | The run light is off. In program or test mode outputs are not written. Check the keyswitch and the mode. |
| Blown fuse on the output module or group | The module indicator is lit but there is no voltage at the terminal. Many modules have a fuse per group and a blown-fuse indicator. Find why it blew before replacing it. |
| No field power to the output common | The output group has no supply on its common, because a branch fuse opened or the field supply is off. Measure the common against DC negative. |
| Interposing relay not pulling in | Voltage at the relay coil and no click. A failed coil, a wrong voltage relay, or a relay base with a bent pin. |
| Wiring open between the panel and the load | Voltage at the panel terminal and none at the load. A broken wire, a loose terminal, or a disconnect in the path. |
| Remote I/O connection lost | The outputs on a remote rack sit at their fault state while the connection is down. The I/O light flashes and the connection shows faulted. |
| The load itself | Voltage at the load and no operation. An open coil, a tripped overload, a motor starter with its own problem. The controller has done its job. |
| Output module failed | The bit is on, the indicator may or may not be lit, and there is no output. Move the load to a spare point; if it works there the module point is dead. |
Work outward from the bit
The most efficient order is the order of the signal: program, module, wiring, load. Each step is one look or one measurement, and each one halves the problem.
- 1
Is the rung true?
Go online and look at the rung that drives the output. If any condition on it is false, the output is off by design, and the problem is upstream of the output entirely. Find which condition and why.
- 2
Is the output bit on?
If the rung is true and the bit is off, look for a force, a second rung writing the same bit later in the scan, or a mode that is not writing outputs. The last rung to write a bit wins.
- 3
Is the module indicator lit?
The LED on the module point follows the output image. Lit means the processor delivered the command to the module. Not lit with the bit on means a module, backplane, or connection problem.
- 4
Is there voltage at the module terminal?
Measure between the output terminal and the return for that group. Indicator lit and no voltage means the group fuse or the field supply to that common.
- 5
Is there voltage at the interposing relay coil, and does it pull in?
Voltage present and no click is the relay. Voltage absent is the wire between the module and the relay.
- 6
Is there voltage at the load?
Measure at the starter coil, the solenoid, or the lamp. Voltage present and no action is the load or its own protection, and the controller is not the problem.
The fuse blew for a reason
A blown output fuse is a symptom. The usual reasons are a shorted coil, a shorted field cable, a load that draws more than the module point can supply, or an inductive load without suppression that has been pitting contacts until one welded. Replacing the fuse without finding the cause blows the new one, sometimes on the first switch. Measure the load resistance and check the wiring insulation before powering it again.
Two ways the program can fool you
- Duplicate outputs
- The same output bit written by two rungs. The last one in the scan decides, and the first one, the one being looked at, is true and apparently ignored. Search the program for every reference to the bit.
- Forces
- A force installed on an output overrides the logic silently. Most software shows a force indicator on the status bar, and it is easy to miss. Check for installed forces early, and remove the ones left over from commissioning.
Remote and distributed I/O
When the output is on a remote rack or a distributed block, one more thing can be wrong: the connection. A remote adapter that has lost its connection to the processor holds its outputs at their configured fault state and ignores the program until the connection returns. The processor may or may not fault, depending on how the connection is configured. The I/O status light, the connection status in the software, and the link light on the adapter tell the story.
Frequently asked questions
- The output shows on in the program but the light on the module is off. What does that mean?
- The processor is not delivering the output image to the module: a force, a mode that is not writing outputs, a lost remote connection, or a failed module or backplane slot. Check forces and mode first, then the I/O status.
- The module light is on but there is no voltage at the terminal.
- The module fuse for that group is open or the field supply to that group common is missing. Measure the common against the supply return, then check the group fuse and the branch fuse feeding it.
- Why would a new fuse blow immediately?
- The fault that blew the first one is still there: a shorted coil or cable, an overloaded point, or an unsuppressed inductive load that has damaged the output. Measure the load and the wiring before replacing the fuse again.
- Can a PLC output drive a motor starter coil directly?
- Some can, within the point rating, but it is poor practice. An interposing relay keeps the coil current and voltage off the module, provides isolation, and fails cheaply. Most panels use one.
Related topics
- PLC I/O SystemsDiscrete and analog input and output modules, sinking and sourcing, relay and transistor outputs, wiring conventions, and the module diagnostics that find field faults from the panel.
- Inputs Not ReadingA switch closes in the field and the program never sees it. How the wetting voltage, the common, sinking and sourcing, and the wiring each lose the signal, and how to find which one did.
- Logic Not Executing As ExpectedThe rung looks right and the plant does something else. The scan-order, duplicate-output, unscheduled-routine, and data-type traps behind it, and how to find which one you are in.
- Fuse Blows RepeatedlyA control fuse that opens again after replacement has a cause the replacement did not touch: a shorted coil, a ground fault in a wet field device, an overloaded circuit, the wrong fuse type for inrush, or an intermittent short. How the timing identifies it.
- Pump Will Not StartA pump that is called and does nothing. The order to check: permissives and mode, control power, the starter or drive, the motor circuit, and the pump itself, with the measurements that settle each one in minutes.
- Processor FaultedA PLC with its fault light on and no logic running. How to read what it is telling you, the causes in order of likelihood, and how to restart it without repeating the fault.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.