Symptom
An analog signal wired in individual conductors or unshielded multiconductor cable is noisy or offset when motors, drives, or heaters run; a serial link on unshielded wire errors; the noise is worst on the longest runs and the ones that share conduit with power.
The short answer
Unshielded Cable in a Noisy Run
An unshielded, untwisted signal cable in a run shared with power or drive conductors picks up capacitive and magnetic noise with nothing to stop it, and the result is an analog reading that wanders when equipment runs or a communication link that errors. Confirm the cable is the cause by laying a temporary shielded twisted pair along the same route and comparing the two readings under the same conditions. The correct fix is shielded twisted pair, grounded at one end, in a route separated by signal class. When the cable cannot be replaced, the alternatives are to convert the signal to 4-20 mA or to a digital link, to isolate and filter at the input, to reduce the source with drive output filtering or a lower carrier frequency, or to move the noisy cable instead.
Key points
- Twisting cancels magnetic pickup; a shield blocks capacitive pickup. Plain conductors have neither.
- Prove it with a temporary cable along the same route before pulling a new one.
- The right fix is shielded twisted pair in a separated route; everything else is a compromise to document.
- 4-20 mA on plain conductors tolerates far more than a voltage signal does; converting the signal can be enough.
- Filtering at the input trades response time for noise; know how much delay the loop can afford.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Individual conductors pulled in a conduit shared with power | Look at the conduit: THHN signal conductors alongside motor conductors is the usual finding in older installations and additions. |
| Unshielded multiconductor cable in a tray with drive cables | Trace the tray run and its length; a long parallel run is worse than a short one by the same factor. |
| Conductors not twisted, so magnetic pickup does not cancel | Inspect the cable construction; parallel conductors in a flat cable or separately pulled wires are the worst case. |
| A voltage signal, 0-10 V or millivolt, on a cable that would be acceptable for 4-20 mA | Check the signal type; the same cable carrying a current loop often works, and the fix is at the ends. |
| Shielded cable in the specification, unshielded installed | Compare the installed cable with the cable schedule; substitutions during construction are common. |
| Long run with high source impedance | A high-impedance signal such as a pH electrode or a thermocouple on unshielded wire is hopeless at any length; check the signal source. |
| Source recently added: a drive or a large motor on a cable that was clean before | Correlate the onset with the change; the cable did not get worse, its neighbors did. |
What the cable is not doing
A twisted pair cancels magnetic coupling because each half twist reverses the polarity of the induced voltage, so the voltages induced along the run cancel in pairs. A shield intercepts the electric field from nearby conductors and carries the displacement current to ground instead of into the signal conductors. Plain conductors do neither: every foot of parallel run adds its induced voltage to the last, and every nearby conductor with a changing voltage injects current straight into the signal wire. In a clean route this does not matter much, which is why plenty of unshielded loops work. In a route with drive cables, motor leads, or contactor wiring, it matters a great deal, and the worse the neighbors and the longer the run, the worse the result.
Prove it first
- 1
Trend the signal
At a fast rate, with the equipment that produces the noise running. Capture a baseline.
- 2
Lay a temporary cable
A shielded twisted pair along the same route, on the floor or draped over the tray, with the shield grounded at the panel end only. Connect the transmitter to it and the input to it, in place of the existing cable.
- 3
Compare
Same equipment running, same trend. If the temporary cable is clean, the installed cable is the problem and replacement is the fix. If the temporary cable is also noisy, the problem is elsewhere: the transmitter, the input, a ground loop, or a source strong enough that routing must change.
- 4
Try the source
If replacement is impractical, briefly stop the drive or lower its carrier frequency and watch. A large improvement points at the drive installation as the alternative fix.
- 5
Decide and document
Replace the cable, change the route, convert the signal, or filter and isolate. Record the choice and why on the loop drawing.
Options when the cable stays
| Option | What it does | Cost and limits |
|---|---|---|
| Convert to 4-20 mA | A current loop is insensitive to induced voltage within the transmitter compliance | Needs a current-output transmitter or a converter at the source; works for most process signals |
| Isolate at the input | Removes common-mode and ground-loop components of the noise | Does nothing for normal-mode pickup; helps when the noise is 60 Hz from ground differences |
| Filter at the input | Hardware or software low-pass removes noise above the filter frequency | Slows the response; a level loop can afford seconds, a pressure loop cannot |
| Move the noisy cable | Removes the source from the route | Often easier than moving the signal cable when the drive cable is short |
| Filter the source | Drive output reactor or sine filter, lower carrier frequency, shielded motor cable | Reduces noise for every signal in the plant, not just this one |
| Go digital | Replace the analog signal with a fieldbus, Ethernet, or fiber link | A larger change; fiber is immune, and Ethernet over shielded cable is far more tolerant than a voltage signal |
| Steel conduit around the signal conductors | Attenuates both coupling mechanisms | Practical only where the conductors can be re-pulled, in which case use shielded cable too |
Filtering with care
A software filter on the input is the fastest fix and the most abused. A first-order filter with a time constant of a few seconds hides 60 Hz and drive-frequency noise completely, and it also hides a real process change for the same few seconds. For a tank level that changes over minutes that is invisible. For a discharge pressure used by a PID loop it adds lag that the loop tuning did not expect, and the loop that was stable becomes oscillatory. Choose the time constant from the process, document it on the loop sheet, and never use a filter to hide a noise problem that will get worse.
Frequently asked questions
- The loop is 4-20 mA on unshielded wire and works fine. Should I replace it anyway?
- If it is clean and the route is not going to get noisier, leave it and note the cable type on the drawing. Current loops on plain conductors are common in older plants and often trouble-free. Replace it the next time the conduit is opened, or the day a drive is installed nearby.
- Can I add a shield by pulling a bare ground wire alongside the conductors?
- No. A drain wire beside the pair is not a shield; a shield surrounds the conductors. Pulling a ground wire in a conduit with the signal conductors does nothing useful and can create a ground loop if it is grounded at both ends.
- Why is my thermocouple hopeless on unshielded wire?
- A thermocouple produces millivolts from a high-impedance source, so a few millivolts of induced noise is a large fraction of the signal. Use shielded thermocouple extension wire, or put a transmitter at the sensor and send 4-20 mA. The same is true of pH electrodes and any other millivolt signal.
- Is it worth twisting the existing conductors by hand at the ends?
- No. Twisting works along the whole run, where the coupling happens; a few twists at the terminals change nothing. Either re-pull twisted shielded cable or use one of the other options.
Related topics
- Cable Routing ProblemsNoise that comes from where a cable runs: signal cables sharing a conduit, tray, or wireway with power or drive cables, long parallel runs, and shallow crossings. How coupling works, the separations that prevent it, and how to find the shared path.
- Common-Mode NoiseNoise that rides on both conductors of a signal pair together, relative to ground: where it comes from, why a differential input rejects it only up to a limit, how to tell it from normal-mode noise with a scope, and the fixes that work.
- Filtering Analog InputsHow to damp a noisy analog input in the controller without hiding a real process change: the first-order filter, the moving average, the median, where each belongs, and what never to filter.
- 4-20 mA Signals from the Instrument SideHow a 4-20 mA current loop is powered and wired at the transmitter, why the loop resistance budget matters, and how to check a loop with a meter.
- 4-20 mA Signal Is UnstableAn analog reading that will not settle. How to separate a genuine process swing from induced noise, a ground loop, or a loop running out of voltage.
- VFD Noise on Analog SignalsAnalog readings that jump or wander when a drive runs, and speed references that make a drive hunt: how the drive output couples into signal wiring, why the input turns kilohertz noise into a slow wander, the tests that pin it on the drive, and the fixes.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.