Symptom
A device is intermittently unreachable or answers with the wrong data; a workstation reports an address conflict; a ping to one address returns replies from two hardware addresses or with alternating response times; a device drops off the network when another is powered on or a laptop is connected.
The short answer
Duplicate IP Address
When two devices on the same network hold the same address, the switches and the other hosts learn whichever answered last, and traffic to that address goes to one or the other unpredictably. The symptoms are intermittent: a controller that answers and then does not, a poll that returns data from the wrong device, a workstation that warns of a conflict, and a device that goes offline exactly when another is powered on. The proof is a ping that returns replies from two different hardware addresses, or an address resolution table that changes between two hardware addresses. The switch address table maps each hardware address to a port, which finds both devices without walking the plant, and the fix is a corrected address on the one that is wrong and a network schedule that says which that is.
Key points
- A ping that returns from two hardware addresses, or an address resolution table that flips, is the proof.
- The switch address table locates both devices by port without a walk.
- Duplicates come from spares, replacements, laptops, cloned images, and address ranges nobody wrote down.
- The network schedule decides which device is wrong; fix that one, never both.
- Static addresses for control devices, a reserved block for them, and a schedule that is kept, prevent the next one.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Replacement device configured with a used address | A spare controller, drive, or radio configured from an old sheet; the original is still on the network or was reused elsewhere. Check the schedule and the address table. |
| Laptop or test device with a static address | A technician laptop set to a plant address for a previous job; the conflict follows the laptop. Assign a dedicated maintenance address. |
| Cloned workstation or virtual machine image | Two machines built from the same image with a static address baked in. Reassign one. |
| Address server range overlapping static addresses | A dynamic address pool that includes addresses assigned statically to controllers; the conflict appears when the pool hands out that address. Exclude the static block from the pool. |
| Device reset to a factory default address | Two devices of the same make both on their default after a reset. Reconfigure to the scheduled addresses. |
| Address reused because the schedule was not updated | A decommissioned device that was not removed from the schedule, or a new device added without one. Reconcile the schedule with the address table. |
| Second interface on a device with the same address | A controller with two ports both configured to one address on one network. Check the device configuration. |
| Gateway address assigned to a device | A device given the router address; the whole network intermittently loses its gateway. Find it in the address table. |
| Wireless bridge or cellular router with a default that matches the plant | A new bridge on its factory address that happens to match a plant device. |
Proving it
- 1
Ping and watch the replies
From a host on the same network, ping the address and look at the replies: two different response times alternating, or duplicate replies to one request, mark two responders.
- 2
Read the address resolution table
On the host, the hardware address recorded for the address; clear the entry, ping again, and read it again. A hardware address that changes between two values is the proof.
- 3
Read the switch address table
On the core switch, the port on which each of the two hardware addresses was learned. Follow each to its access switch and port.
- 4
Identify the devices
The hardware address prefix names the manufacturer; the port on the network drawing names the cabinet. Confirm at the device.
- 5
Decide which is wrong
The network schedule says who owns the address. The other device is corrected; if the schedule is silent, it is written before anything changes.
- 6
Fix and verify
Change the wrong address, clear the address tables, ping, and confirm one hardware address. Update the schedule.
ping 192.168.10.20 -t
arp -a 192.168.10.20
arp -d 192.168.10.20 (then ping again and read arp -a again)
switch# show mac address-table address <hardware address>| Hardware address changes | Response times | Meaning |
|---|---|---|
| Yes | Alternating or doubled | Two devices on one address: duplicate confirmed |
| No | Stable | One device; the intermittent symptom is elsewhere |
| No | Occasional long | One device that is slow or a link with loss |
| Yes, one of them is the router | Any | A device holding the gateway address: urgent |
Where duplicates come from
Almost every duplicate is a discipline failure rather than a mystery: an address was assigned twice because nobody had the list, or was reused because the list was wrong, or was set on a laptop and forgotten. The plant that never has them keeps one network schedule per network with every address, the device that holds it, its hardware address, and the cabinet and port; assigns static addresses to every control device from a block that the address server never touches; gives maintenance laptops their own addresses; and updates the schedule as part of the change, not afterward.
Preventing the next one
- One network schedule per network, kept in the engineering library, with hardware addresses recorded at commissioning.
- A static block for controllers, drives, instruments, and radios, excluded from every dynamic address pool.
- A dedicated address, or a dedicated maintenance network, for laptops and test equipment.
- Replacement procedure that reads the address from the schedule, not from the label on the old device, and updates the hardware address.
- Periodic reconciliation of the switch address tables against the schedule; a device on the network that is not on the schedule is a finding.
Frequently asked questions
- The conflict only happens when a particular laptop is plugged in.
- The laptop holds the address. Change the laptop to the maintenance address and record it. The controller was never the problem.
- How can two devices with the same address both seem to work sometimes?
- Each switch and host learns the last hardware address that spoke, so traffic goes to whichever device most recently sent a frame. Two quiet devices can trade the address back and forth for hours, each working part of the time.
- Does an address server prevent duplicates?
- It prevents them among the devices it serves, and it causes them when its pool overlaps the static addresses of the devices it does not. Control devices are static and excluded from the pool; the server handles workstations and visitors.
- What if the duplicate is on the gateway address?
- Every device on the network intermittently loses its route off the network; it is the most disruptive duplicate and the first to fix. The address table finds the impostor, which is usually a device set up from a form where someone typed the gateway into the address field.
Related topics
- How to Assign IP Addresses on a Control NetworkBuild an addressing plan before the first device is configured: one subnet per zone and site, a fixed block layout so an address says what the device is, static addresses on everything that controls a process, and a schedule that is kept current.
- Network SchedulesThe tables behind the network drawings: the address schedule of every device, the switch port schedule of every port, the VLAN table, and the conduit list of what the firewalls permit. How they are built, kept as the single source of truth, and protected.
- Ethernet Device Drops OfflineAn industrial Ethernet device that disappears and comes back. Duplex mismatch, cabling, spanning tree, and the switch counters that identify it in minutes.
- Cannot Ping Across VLANsTwo devices that work on their own networks but cannot reach each other across a VLAN boundary: no route, a wrong or missing gateway, a mask that puts the target on the wrong side, a trunk missing the VLAN, or a firewall rule. Testing each in order.
- Device Times OutA polled device that answers late or not at all: how to read the driver counters, tell a dead device from a slow one, and find the timeout setting, the bus loading, the radio latency, the duplicate address, or the device that is simply too busy to answer.
- Tag Shows Bad QualityA tag flagged bad or uncertain by the driver. What the quality codes mean, the difference between a device that is not answering and an address that does not exist, and how to clear each.