Symptom
The transmitter display is lit and shows a value; the controller input reads zero, under-range, or open; the loop is new, was just rewired, or the input module or transmitter was replaced; the loop may read correctly on a meter at the transmitter but not at the controller.
The short answer
Loop Powers Up but Reads Zero
A transmitter that lights up is being powered, but the controller only reads what flows through its input, and a loop can be complete for power while broken for signal. The commonest reasons are wiring that puts the transmitter across the supply without the input in series, an active input driving a transmitter that also supplies power so that the two fight, a missing jumper or configuration that leaves the channel dead, an input fuse that has opened, or a transmitter that is powered but not producing an output because of a fault or a configuration. A meter in series at the input terminals answers the first question: whether current is flowing through the input at all. If it is, the module or its configuration is the problem; if it is not, the loop wiring or the transmitter output is.
Key points
- A lit transmitter proves power, not signal; measure the current through the input.
- A two-wire transmitter needs the supply, the transmitter, and the input all in one series loop.
- An input that sources loop power must not be wired to a loop that already has a supply, and a passive input must be wired to one that does.
- Modules with jumpers or channel configuration for current mode read zero when they are left in the voltage mode.
- The transmitter can be powered and still send nothing: a fault, an output turned off, or a multidrop address.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Input not in the series loop | The transmitter is wired across the supply and the input is connected to only one side or to the wrong terminals; current flows around the input. Trace the loop as one circuit. |
| Active and passive mismatch | A loop-powered transmitter on an input that also sources power, or a passive input on a loop with no supply; the current is zero or wrong. Check what supplies the loop and wire for exactly one source. |
| Module jumper or channel mode | The channel set for voltage while the loop is current, or a current-mode jumper missing; the input sees the voltage across nothing. Set the channel and the jumper for current. |
| Input fuse or protection open | Some modules fuse each channel; a shorted loop during wiring opened it. Check the module manual for a channel fuse. |
| Reversed input polarity | The input reads zero or a negative count with the current present. Swap the input leads and read the counts. |
| Channel not configured or disabled | The module is present but the channel is not enabled in the configuration, or it is configured for a different range. Check the module configuration. |
| Transmitter output disabled or in a fault | The transmitter shows a value but its output is off, in a simulation, or driven to a fault current that the input interprets as zero; a communicator shows the output state. |
| Multidrop or digital mode | A transmitter set to multidrop address other than zero fixes its output at 4 milliamps or turns it off; check the polling address. |
| Isolator or barrier miswired | A device between the transmitter and the input wired on the wrong side or not powered; measure on both sides. |
| Shunt resistor missing or wrong | On a voltage input used for current, the resistor across the input is missing or open; the input sees no voltage. Fit the correct resistor. |
One circuit
A two-wire loop is one series circuit: the positive of the supply to the positive of the transmitter, the negative of the transmitter to the positive of the input, the negative of the input back to the negative of the supply. The transmitter regulates the current in that circuit to represent the measurement, and every device in the circuit sees the same current. Anything that takes the input out of the series path leaves the transmitter powered and the input empty, and it happens in a junction box with three terminals more often than anyone admits.
| Where the meter goes | Reads | Meaning |
|---|---|---|
| In series at the transmitter | 4 to 20 mA | Transmitter is producing a signal |
| In series at the transmitter | 0 mA | Transmitter output off, in fault, or multidrop; or the loop is open despite the display |
| In series at the input terminals | Same as at the transmitter | Signal reaches the input; the module or its configuration is the problem |
| In series at the input terminals | 0 mA with current at the transmitter | The current bypasses the input: wiring |
| Voltage across the input | 1 to 5 V on a 250 ohm input | Current is flowing through the input |
| Voltage across the input | Supply voltage | Input is open: fuse, jumper, or a broken lead inside the module |
Working it
- 1
Series current at the transmitter
Break the loop at the transmitter negative and read current with the meter in series. If it is zero, the transmitter is powered but not driving; if it is live, continue.
- 2
Series current at the input
Break the loop at the input positive terminal and read again. Equal to the transmitter current means the loop is complete through the input.
- 3
Voltage across the input
With the loop connected, the voltage across the input terminals: about 1 to 5 volts for a 250 ohm input at 4 to 20 milliamps; the full supply voltage means the input is open.
- 4
Module configuration
Channel enabled, current mode, correct range, any jumper set for current, the raw counts in the controller.
- 5
Wiring
Trace the loop as one circuit through every terminal strip and junction box; look for the input connected in parallel with the supply or on one side only.
- 6
Transmitter
Output state, loop test or simulation mode, multidrop address, fault code; a loop test that drives 12 milliamps proves the output.
Replacement traps
- A replacement module of a different type: active where the old one was passive, or a different terminal arrangement.
- A replacement transmitter left in multidrop mode or with the output disabled from bench testing.
- A three-wire or four-wire transmitter wired as two-wire, with the signal terminals unused.
- A voltage input reused for current without the shunt resistor, or with a resistor of the wrong value.
- An isolator installed with the loop powered from the wrong side.
Frequently asked questions
- The transmitter display shows 12 mA. Why does the controller see zero?
- The transmitter is reporting what it is trying to drive, not what the input receives. The current is bypassing the input or the input is not reading it: measure in series at the input terminals and read the voltage across the input.
- The input reads a small negative number.
- The polarity at the input is reversed; the current is flowing but the wrong way through the input. Swap the two leads at the input.
- I get 24 volts across the input terminals.
- The input is open. The channel fuse, a jumper set for voltage mode, a missing shunt resistor on a voltage input, or a failed input circuit. The supply is pushing against an open and no current flows.
- Can I test the loop without the transmitter?
- Yes: a loop calibrator in place of the transmitter, set to simulate a two-wire transmitter, drives a known current through the loop. The controller should follow it. If it does, the transmitter is the problem; if it does not, the loop or the input is.
Related topics
- How to Test a 4-20 mA LoopProve a current loop end to end with a meter and a calibrator, without interrupting a process you were not authorized to interrupt.
- 4-20 mA Signals from the Instrument SideHow a 4-20 mA current loop is powered and wired at the transmitter, why the loop resistance budget matters, and how to check a loop with a meter.
- 4-20 mA Current LoopsWhy the industry standardized on current instead of voltage, how a two-wire loop is powered, what the live zero buys you, and how to read a loop with a meter.
- Signal Pegged High or LowA 4-20 mA signal stuck at a rail or a fault current: a transmitter in fault, a process truly out of range, an open or shorted loop, a wrong range, a wiring error, an input channel fault, or a scaling clamp. How the current itself tells you which.
- I/O Not UpdatingInputs that do not change and outputs that do not respond while the controller runs: the module and rack status, the inhibited and faulted connections, the input filter and the scan, the remote adapter link, the forced points, and the program that stopped writing the tag.
- Loop ChecksProving every I/O point end to end before a system goes live: what a loop check is and is not, the three-point analog check, discrete and output checks, the two-person method with the sheet that records it, what to do with a point that fails, and why a loop check is not a calibration.