Shield Grounded at Both Ends

A shield connected to ground at the panel and again in the field becomes a conductor between two grounds, and its current becomes noise on the pair inside. How to find the second connection, what to measure before lifting it, and when both ends are correct.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

Symptom

Hum or a shifting offset on an analog signal, noise that appears when large loads switch, a warm or discolored drain wire, or a burned shield after a storm; the shield at the panel measures continuity to ground after it has been lifted.

The short answer

Shield Grounded at Both Ends

For instrument signal cables the shield is grounded at one end only, normally the panel end, and insulated at the field end. A shield grounded at both ends carries whatever current the potential difference between the two grounds drives through it, and that current couples into the signal conductors as hum and offsets, and in a lightning or fault event can burn the drain wire. Find the second connection by lifting the shield at the panel and measuring resistance from shield to ground, which should be open; measure the shield current with a clamp first, because the value tells you how large the ground potential difference is. High-frequency cables such as Ethernet, fieldbus, and drive motor cables are bonded at both ends by design and are the exception.

Key points

  • Instrument cable shields: one ground, at the panel, with the field end insulated and taped.
  • Both ends grounded turns the shield into a ground conductor, and its current couples into the pair.
  • Test by lifting the panel end: shield to ground should read open. Clamp the shield for current before lifting.
  • The second connection is usually at the transmitter terminal, in a junction box, or a bare drain touching a gland.
  • Ethernet, fieldbus, and drive motor cables are bonded at both ends on purpose; do not apply the instrument rule to them.

Possible causes and what to check

Possible causeWhat to check
Drain wire landed on the transmitter ground or shield terminal in the fieldOpen the transmitter housing and look. Many transmitters have a shield terminal connected to the case; the manual says whether it is isolated.
Bare drain wire touching the housing inside a cable gland or conduit fittingInspect where the cable enters the housing. A drain wire that is not sleeved finds metal.
Shield landed on the ground bar in a junction boxJunction boxes between field and panel are the most common place for a second ground; shields should be carried through on an isolated terminal.
Shield connected to ground through a connector shell or a metal-bodied terminalConnector shells and some terminal styles bond the shield to the mounting rail. Check with the cable disconnected.
Shield continued through a splice to a second cable that is groundedTrace splices; every shield segment should be continuous to the panel and open to ground everywhere else.
Panel end grounded twice, at the entry gland and at the terminalGrounding twice inside one panel is harmless if both points are on the same bus; it is a loop only if they are on different grounds.
Large ground potential difference making even a small shield leak matterMeasure AC and DC volts between the panel ground and the field ground after lifting the shield. Several volts is a grounding system problem to fix as well.

What a shield is for

A shield around a twisted pair is a barrier against electric field coupling. Grounded at one end it holds the field at ground potential without carrying current; capacitive noise that would have reached the conductors is drained to ground instead. It is not there to carry current, and it is not part of the signal circuit. Grounded at both ends it is a conductor in parallel with the plant grounding system, and whatever voltage exists between the two ground points drives current through it. At 60 Hz that current produces a magnetic field around the shield that induces voltage in the pair inside, and the shield resistance times the current appears as a voltage at the signal end if the shield is also the reference. In a lightning event the shield tries to carry the surge current, and a drain wire is not sized for that.

Which end

The convention for instrument signals is the panel end, because the panel ground bus is the reference for the input circuits and is the better ground. The field end is cut back, insulated with heat shrink or tape, and left unconnected. At a junction box the shield passes through on an isolated terminal, still with one ground at the panel. A transmitter with a metal housing sees the shield insulated inside the housing, not landed on the housing ground.

CableShield practiceReason
4-20 mA, HART, RTD, thermocouple, 0-10 VOne end, at the panelLow-frequency signals; the shield is a capacitive barrier, not a return
RS-485 and RS-232One end as a rule; both only where the manufacturer specifies and the grounds are bondedCommon-mode limits are small; ground current on the shield is worse than the noise it blocks
Shielded EthernetBoth ends, through the connector shellsHigh-frequency shield performance requires low impedance at both ends
Fieldbus such as Profibus DPBoth ends, 360 degree clamp at every deviceManufacturer requirement; the network depends on it
Drive to motor cableBoth ends, 360 degree bond at the drive and the motorThe shield is the return path for high-frequency drive current, keeping it off the plant ground
Coaxial antenna feedBonded at the entry to the buildingLightning protection, per the radio and surge protector instructions

Diagnostic procedure

  1. 1

    Clamp the shield

    Before lifting anything, put a sensitive clamp meter around the drain wire at the panel end. A shield with one ground carries no measurable current. Tens of milliamps or more means it is a conductor between two grounds.

  2. 2

    Lift the panel end

    Disconnect the shield drain from the panel ground and measure resistance from the drain to ground. Open, above a megohm, means the field end is insulated. Continuity means there is a second connection somewhere.

  3. 3

    Measure the potential

    With the shield lifted, measure AC and DC volts from the drain to the panel ground. That is the voltage between the field ground and the panel ground. A few hundred millivolts is normal; several volts means the grounding system has a fault worth finding.

  4. 4

    Find the second connection

    Work from the panel toward the field: junction boxes, splices, glands, the transmitter housing. Disconnect the shield at each point and measure again toward the field until the continuity disappears.

  5. 5

    Insulate it

    Cut the drain back, sleeve it, and tape or heat shrink so it cannot touch metal. Reconnect the panel end.

  6. 6

    Verify

    Clamp the shield again; the current should be gone. Watch the signal for the noise or offset that started the investigation, with the loads that made it worse running.

Fixing the cause, not just the loop

A shield grounded at both ends only causes trouble when there is a potential difference between the grounds. A large difference means the grounding system is carrying current it should not: neutral current from a wrong bond, drive current returning through the earth, or two buildings with no bonding between them. Insulating the shield end removes the symptom on one signal; correcting the grounding system removes it for every signal in the plant.

Frequently asked questions

The manufacturer says to ground the shield at the transmitter. Who is right?
Follow the manufacturer for that device, and then do not ground the same shield at the panel. The rule is one ground per shield, and some transmitters, particularly ones with radio frequency protection built in, are designed for the shield to terminate at the device. What is never right is both.
Is it acceptable to leave a shield unconnected at both ends?
It does nothing then, and the pair is unshielded. Connect it at one end. A shield with no ground can also float up to a voltage through capacitance and give a surprising tingle from a long cable.
Why are drive motor cables bonded at both ends when instrument cables are not?
Because the motor cable shield has a different job: it is the return path for the high-frequency current the drive pushes through the motor cable capacitance. Bonded at both ends with a 360 degree connection, that current stays in the cable instead of returning through the plant ground, where it would raise the potential differences that cause instrument problems.
Can I ground shields on a common bar with everything else in the panel?
Yes, if that bar is bonded to the panel ground bus, which is the reference for the analog inputs. Some designs use a separate instrument ground bar tied to the main bus at one point; that is fine too. The point is one connection to one ground per shield.

Direct contact