Symptom
A switch port or media converter shows no link on a fiber connection; the link light is dark at one end or both; devices beyond the link are unreachable; the loss followed excavation, a storm, cabinet work, or a transceiver swap.
The short answer
Fiber Link Down
A fiber link that shows no link on either end has lost light in one direction or both, and the receive power reading at each end says which. No light at either end with both transmitters alive means the fiber between them is cut, disconnected, or reversed; light at one end only means the other transmitter, its transceiver, or the strand carrying it is the fault. A link with light at both ends and no link state has a transceiver, speed, or port configuration problem rather than a cable problem. Work from the port state and the optical power at both ends, then the patch cords and connectors, then the transceivers by substitution, and send an optical time domain reflectometer down the cable only when the plant is clean and the fault is in the outside plant.
Key points
- Receive power at each end tells you which direction has lost light before anything is touched.
- A cut cable takes both directions; a failed transmitter takes one.
- Reversed transmit and receive strands are the first thing to try after any patch cord work.
- A transceiver pair must match in wavelength, mode, and speed; a port must be enabled and set for the media.
- An optical time domain reflectometer locates a break in the outside plant to within a few meters.
Possible causes and what to check
| Possible cause | What to check |
|---|---|
| Cable cut, crushed, or pulled from a splice | No receive power at either end with both transmitters alive; a recent excavation, a storm, a vehicle strike on a pedestal, or work in the manhole. An optical time domain reflectometer trace shows the break distance. |
| Patch cord disconnected or strands reversed | The link died during cabinet work; swap transmit and receive at one end and watch the link lights. Check every patch panel and coupler in the run. |
| Transceiver failed or not seated | No transmit power at one end; the module reads no transmit or is not recognized by the switch. Reseat, then substitute a known-good module of the same type. |
| Transceiver pair mismatched | Different wavelengths, single-mode against multimode, or different speeds at the two ends. Read the module part numbers and the wavelength on each. |
| Port disabled, misconfigured, or negotiating wrong | Light present at both ends but no link: the port is administratively down, forced to a speed the module cannot do, or set for copper on a combo port. Check the port configuration on both switches. |
| Media converter without power or in the wrong mode | The converter indicators; its supply and fuse; a mode switch set to link fault pass-through so that a fault on one side drops the other. |
| Connector dirty or damaged | Receive power far below the record at one end while the other reads normal; a connector that was left uncapped. Inspect, clean, and remeasure. |
| Bend or crush in the patch cord or cabinet | A cord pinched by a door or a tie wrap, or bent tighter than its minimum radius; loss appears in one direction first. |
| Wrong fiber or wrong pair at a patch panel | A cross-connect landed on the wrong port after work; trace the pair against the fiber schedule and test it end to end. |
Read the link before touching it
Every managed switch and most media converters report the transceiver state: transmit power, receive power, temperature, and whether the module is recognized. The pattern across the two ends is the diagnosis, and it takes a minute from a desk. Record what it says before anyone opens a cabinet, because the first person to reseat a cord destroys the evidence.
| End A receive | End B receive | Both transmit | Most likely |
|---|---|---|---|
| None | None | Normal | Cable cut or both strands disconnected or reversed |
| None | Normal | Normal | The strand from B to A: a bad strand, a cord, or a connector on that direction |
| None | Normal | B transmit absent | The transceiver at B has failed or is not seated |
| Normal | Normal | Normal | Not the fiber: port configuration, speed, module mismatch, or a switch problem |
| Low at one end | Normal | Normal | A dirty or damaged connector, a bend, or a bad splice on one direction |
| No module recognized | Any | Any | Transceiver unsupported, failed, or not seated |
Working outward
- 1
Port state
Is the port enabled, is the module recognized, is the speed forced or negotiated, and does the far switch agree. A port that was shut down by a loop protection or a security feature shows a reason in the log.
- 2
Optical power
Transmit and receive at both ends against the commissioning record. Compare, do not just read: a link that ran at minus twelve decibel-milliwatts and now reads minus thirty has lost eighteen decibels somewhere.
- 3
Patch cords
Reseat, then swap transmit and receive at one end. A reversed pair after cabinet work is the most common cause of a dead link that used to work.
- 4
Connectors
Inspect with a scope and clean every connector in the run, both sides of every coupler. A single dirty connector can take the whole link budget.
- 5
Transceiver
Substitute a known-good module of the same part number at the end with no transmit power. Then at the other end.
- 6
The run
If the plant is clean and the light is still gone, the fault is between the patch panels: a splice enclosure, a pedestal, a duct crossing. An optical time domain reflectometer from the patch panel gives the distance to the break.
When the cable is cut
A break in the outside plant is found with the reflectometer trace, the fiber schedule, and the as-built route. The trace gives a distance in fiber meters, which is longer than the ground distance because of slack loops and the cable helix, and the route drawing turns that into a place to dig. A break at a splice enclosure is repaired in the enclosure; a break in the run is repaired with a splice case and enough slack, or the cable is replaced between pedestals. The repaired link is tested end to end with a light source and power meter and the loss recorded against the budget.
Preventing the next one
- Label both ends of every strand and keep the fiber schedule current, so a cross-connect after work lands where it should.
- Cap every unused port and cord; a connector left open in a cabinet collects the dust that takes it down a year later.
- Keep the commissioning power readings with the switch documentation. The comparison is the diagnosis.
- Locate and mark buried routes before excavation on site; most cut fiber was cut by someone who did not know it was there.
- Carry a spare transceiver of each type in use and a cleaning kit; most fiber visits end with one or the other.
Frequently asked questions
- The link light is on at one end and off at the other. Which end is broken?
- The end whose light is off is not receiving; the fault is on the strand that feeds it, or in the transmitter at the other end. Read the transmit power at the lit end: if it is normal, the strand or a connector on that direction is the problem; if it is absent, the transceiver there has failed.
- Both ends show good receive power but no link.
- The fiber is fine. Look at the port configuration: speed, duplex, autonegotiation, and whether the port is administratively down or was shut by a protection feature. Then confirm the two transceivers are the same speed and that the switch supports the module.
- Can I test the fiber with a flashlight?
- A visible light source at one end and an eye at the far patch panel confirms continuity and finds a reversed pair on a short multimode run, but it says nothing about loss. A visual fault locator does the same job properly and also lights up a tight bend or a break through the jacket on a patch cord.
- The reflectometer says the break is at 640 meters but the route is only 500 meters long.
- Fiber distance exceeds route distance: slack loops at each end and at every splice, the cable lay, and the reflectometer calibration for the fiber refractive index. Apply the as-built slack from the fiber schedule and use the index of refraction from the cable data sheet.
Related topics
- High Optical LossA link that is up but running near the receiver floor: the loss budget from transmitter to receiver and what ate it. Dirty connectors, bad splices, tight bends, a run too long for the module, or a wrong fiber type. Measuring the loss and getting margin back.
- Dirty or Damaged ConnectorThe most common fiber fault: a connector end face with dust, oil, or a scratch that takes decibels from the link and damages its mate. How to inspect with a scope, what contamination and damage look like, how to clean properly, and when to replace it.
- Wrong Fiber Type or WavelengthA link that will not come up, or runs with high loss, because parts do not match: single-mode modules on multimode fiber, a multimode cord in a single-mode run, mixed grades, different wavelengths, or a same-wavelength bidirectional pair. Reading the markings.
- Fiber SchedulesThe record of every fiber strand between every pair of patch panels: cable identifiers, strand numbers and the standard color sequence, fiber type, connectors, what each strand carries, splices, lengths, and test results, with the labeling that matches it.
- Ethernet Device Drops OfflineAn industrial Ethernet device that disappears and comes back. Duplex mismatch, cabling, spanning tree, and the switch counters that identify it in minutes.
- Network DrawingsThe two drawings every control network needs: a logical drawing of zones, subnets, VLANs, firewalls, and conduits, and a physical drawing of switches, ports, cables, fiber, radios, and sites. What each shows and why they are sensitive.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.