Ambient Temperature Correction Factors

Multipliers applied to conductor ampacity when the ambient temperature differs from 30 degrees C, by insulation temperature rating.

Source of these values

Values as commonly published for NFPA 70 Table 310.15(B)(1), based on 30 degrees C. Verify against your adopted edition.

Ambient CAmbient F60 C rated75 C rated90 C rated
10 or less50 or less1.291.21.15
11 to 1551 to 591.221.151.12
16 to 2060 to 681.151.111.08
21 to 2569 to 771.081.051.04
26 to 3078 to 86111
31 to 3587 to 950.910.940.96
36 to 4096 to 1040.820.880.91
41 to 45105 to 1130.710.820.87
46 to 50114 to 1220.580.750.82
51 to 55123 to 1310.410.670.76
56 to 60132 to 140—0.580.71
61 to 65141 to 149—0.470.65
66 to 70150 to 158—0.330.58
71 to 75159 to 167——0.5
76 to 80168 to 176——0.41
81 to 85177 to 185——0.29

In short

Conductor ampacity tables assume a 30 degree C ambient. Above that, ampacity is reduced by a correction factor: a 75 degree C conductor is multiplied by 0.94 between 31 and 35 degrees C, and by 0.82 between 41 and 45 degrees C. Below 30 degrees C the factors are greater than one.

Notes and limits

  • A dash means the conductor is not usable at that ambient temperature and a higher insulation rating is required.
  • The ambient to use is the temperature the conductor actually sees, which inside a sealed enclosure in the sun is well above the outdoor temperature.
  • This factor and the adjustment factor for conductor count both apply, multiplied together.