Electrical
Ambient Temperature Correction Factors
Multipliers applied to conductor ampacity when the ambient temperature differs from 30 degrees C, by insulation temperature rating.
Source of these values
Values as commonly published for NFPA 70 Table 310.15(B)(1), based on 30 degrees C. Verify against your adopted edition.
| Ambient C | Ambient F | 60 C rated | 75 C rated | 90 C rated |
|---|---|---|---|---|
| 10 or less | 50 or less | 1.29 | 1.2 | 1.15 |
| 11 to 15 | 51 to 59 | 1.22 | 1.15 | 1.12 |
| 16 to 20 | 60 to 68 | 1.15 | 1.11 | 1.08 |
| 21 to 25 | 69 to 77 | 1.08 | 1.05 | 1.04 |
| 26 to 30 | 78 to 86 | 1 | 1 | 1 |
| 31 to 35 | 87 to 95 | 0.91 | 0.94 | 0.96 |
| 36 to 40 | 96 to 104 | 0.82 | 0.88 | 0.91 |
| 41 to 45 | 105 to 113 | 0.71 | 0.82 | 0.87 |
| 46 to 50 | 114 to 122 | 0.58 | 0.75 | 0.82 |
| 51 to 55 | 123 to 131 | 0.41 | 0.67 | 0.76 |
| 56 to 60 | 132 to 140 | — | 0.58 | 0.71 |
| 61 to 65 | 141 to 149 | — | 0.47 | 0.65 |
| 66 to 70 | 150 to 158 | — | 0.33 | 0.58 |
| 71 to 75 | 159 to 167 | — | — | 0.5 |
| 76 to 80 | 168 to 176 | — | — | 0.41 |
| 81 to 85 | 177 to 185 | — | — | 0.29 |
In short
Conductor ampacity tables assume a 30 degree C ambient. Above that, ampacity is reduced by a correction factor: a 75 degree C conductor is multiplied by 0.94 between 31 and 35 degrees C, and by 0.82 between 41 and 45 degrees C. Below 30 degrees C the factors are greater than one.
Notes and limits
- A dash means the conductor is not usable at that ambient temperature and a higher insulation rating is required.
- The ambient to use is the temperature the conductor actually sees, which inside a sealed enclosure in the sun is well above the outdoor temperature.
- This factor and the adjustment factor for conductor count both apply, multiplied together.