How to Design Panel Grounding

Design the grounding and bonding of a control panel and its site so that faults clear, signals are clean, and surges have a path: bond the enclosure and everything in it, and verify with measurements before the panel is energized.

8 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

How to Design Panel Grounding

To design panel grounding, start with the safety ground: the enclosure, the sub-panel, the doors with devices, and every metal part bonded together and to the equipment grounding conductor of the supply, with a ground bar for the field equipment grounding conductors; then add the reference grounds: an instrument ground bar for the 24 volt common and the shield drains, bonded to the enclosure ground at one point by a short conductor so that it is at ground potential without carrying fault or noise current, and a surge entrance bar bonded to the same point and to the site electrode system by the shortest path; make sure the site electrodes, the service ground, the mast ground, and the panel ground are all bonded together so that no two grounds at the site can be at different potentials; draw all of it on a grounding diagram with conductor sizes and the single bond points; and verify at commissioning with bond resistance and electrode resistance measurements, recorded.

Key points

  • Safety first: everything metal bonded and the equipment grounding conductors on a bar bonded to the supply ground.
  • Reference grounds, the instrument bar and the shield bar, bonded to the safety ground at one point by a short conductor.
  • The surge entrance bar bonded to the same point and to the site electrodes by the shortest path.
  • All site electrodes bonded together: service, panel, mast, and any rods; no isolated grounds.
  • A grounding diagram with sizes and bond points, verified by measurement at commissioning.

What you need

  • The panel schematic and layout, and the site electrical one-line
  • The electrical code articles on grounding and bonding, and the panel listing standard requirements
  • The surge device manufacturer bonding requirements
  • Ground bars, bonding jumpers, and lugs sized per the code
  • A ground resistance tester and a low-resistance ohmmeter for verification

Procedure

  1. 1

    Bond the enclosure

    The enclosure body, the sub-panel, and each door carrying devices bonded together with bonding jumpers or straps, through paint-cutting hardware, and the enclosure bonded to the equipment grounding conductor of the supply at a lug sized per the code.

  2. 2

    Provide the equipment ground bar

    A bar bonded to the enclosure, with a terminal for every outgoing circuit equipment grounding conductor, sized for the largest conductor, near the power terminals.

  3. 3

    Ground the control transformer secondary

    One side of the 120 volt control circuit bonded to the enclosure at the transformer, per the design, so that a ground fault on the control circuit clears a fuse.

  4. 4

    Ground the 24 volt common

    The negative of the 24 volt supply bonded to the instrument ground bar; one bond per isolated supply; the bar bonded to the enclosure ground at one point with a short conductor.

  5. 5

    Provide the instrument and shield bar

    A bar, insulated from the enclosure and bonded to it at the single point, with terminals for the shield drains of every analog and communication cable, grounded at the panel end only.

  6. 6

    Provide the surge entrance bar

    At the conductor entrance, a bar the surge devices land on, bonded to the enclosure ground and to the site electrode system by the shortest, straightest conductor the layout permits, sized per the device manufacturer.

  7. 7

    Bond the site

    The service ground, the panel ground, the radio mast ground, any ground rods, and the building steel bonded together so that the site has one ground system. A separate rod for the radio is bonded to the rest; an isolated ground is prohibited.

  8. 8

    Handle special cases

    Intrinsically safe Zener barriers with their dedicated ground per the control drawing; drives with the motor cable shield bonded at both ends per the drive manual and the drive chassis bonded; isolated instrument grounds only where a design requires them, still bonded.

  9. 9

    Draw it

    A grounding diagram showing every bar, every bond, the single points, the conductor sizes, and the site electrodes; the drawing in the panel set.

  10. 10

    Verify

    At commissioning: bond resistance from the enclosure and each bar to the supply ground in the milliohm range with a low-resistance ohmmeter; site electrode resistance with a ground tester and the value recorded; no voltage between the instrument bar and the enclosure with the plant running; every shield grounded at one end only.

GroundPurposeBonded toRule
Enclosure and equipment ground barSafety; fault clearingSupply equipment grounding conductorEverything metal; sized per the code
Control circuit groundFault clearing on 120 volt controlEnclosure at the transformerOne side of the secondary
Instrument ground barReference for 24 volt common and shieldsEnclosure at one pointSingle bond; no fault current
Shield barShield drainsInstrument barShields grounded at the panel end only
Surge entrance barSurge current pathEnclosure ground and site electrodesShortest path; sized per the device
Site electrode systemEarth reference and lightningService, panel, mast, rods, steelAll bonded together

Frequently asked questions

Should the instrument ground have its own rod?
No. A separate rod that is not bonded to the rest is an isolated ground and a hazard; the instrument ground is a bar bonded to the enclosure ground at one point. If a rod is installed for the instrument bar, it is bonded to the site electrode system too.
Where do the cable shields go?
On the shield bar at the panel end, with the field end insulated. A shield grounded at both ends carries ground loop current and noise into the signal.
How low should the electrode resistance be?
As low as the site allows, with the code and the surge device requirements as the reference; more important is that every electrode at the site is bonded together. Record the measured value and retest periodically.
The drive manual says bond the motor cable shield at both ends. Does that contradict the shield rule?
No. The drive output cable shield is a power circuit shield carrying high-frequency current back to the drive and is bonded at both ends per the drive manual. Signal shields are grounded at one end. Different circuits, different rules.

Direct contact