The short answer
How to Design Panel Grounding
To design panel grounding, start with the safety ground: the enclosure, the sub-panel, the doors with devices, and every metal part bonded together and to the equipment grounding conductor of the supply, with a ground bar for the field equipment grounding conductors; then add the reference grounds: an instrument ground bar for the 24 volt common and the shield drains, bonded to the enclosure ground at one point by a short conductor so that it is at ground potential without carrying fault or noise current, and a surge entrance bar bonded to the same point and to the site electrode system by the shortest path; make sure the site electrodes, the service ground, the mast ground, and the panel ground are all bonded together so that no two grounds at the site can be at different potentials; draw all of it on a grounding diagram with conductor sizes and the single bond points; and verify at commissioning with bond resistance and electrode resistance measurements, recorded.
Key points
- Safety first: everything metal bonded and the equipment grounding conductors on a bar bonded to the supply ground.
- Reference grounds, the instrument bar and the shield bar, bonded to the safety ground at one point by a short conductor.
- The surge entrance bar bonded to the same point and to the site electrodes by the shortest path.
- All site electrodes bonded together: service, panel, mast, and any rods; no isolated grounds.
- A grounding diagram with sizes and bond points, verified by measurement at commissioning.
What you need
- The panel schematic and layout, and the site electrical one-line
- The electrical code articles on grounding and bonding, and the panel listing standard requirements
- The surge device manufacturer bonding requirements
- Ground bars, bonding jumpers, and lugs sized per the code
- A ground resistance tester and a low-resistance ohmmeter for verification
Procedure
- 1
Bond the enclosure
The enclosure body, the sub-panel, and each door carrying devices bonded together with bonding jumpers or straps, through paint-cutting hardware, and the enclosure bonded to the equipment grounding conductor of the supply at a lug sized per the code.
- 2
Provide the equipment ground bar
A bar bonded to the enclosure, with a terminal for every outgoing circuit equipment grounding conductor, sized for the largest conductor, near the power terminals.
- 3
Ground the control transformer secondary
One side of the 120 volt control circuit bonded to the enclosure at the transformer, per the design, so that a ground fault on the control circuit clears a fuse.
- 4
Ground the 24 volt common
The negative of the 24 volt supply bonded to the instrument ground bar; one bond per isolated supply; the bar bonded to the enclosure ground at one point with a short conductor.
- 5
Provide the instrument and shield bar
A bar, insulated from the enclosure and bonded to it at the single point, with terminals for the shield drains of every analog and communication cable, grounded at the panel end only.
- 6
Provide the surge entrance bar
At the conductor entrance, a bar the surge devices land on, bonded to the enclosure ground and to the site electrode system by the shortest, straightest conductor the layout permits, sized per the device manufacturer.
- 7
Bond the site
The service ground, the panel ground, the radio mast ground, any ground rods, and the building steel bonded together so that the site has one ground system. A separate rod for the radio is bonded to the rest; an isolated ground is prohibited.
- 8
Handle special cases
Intrinsically safe Zener barriers with their dedicated ground per the control drawing; drives with the motor cable shield bonded at both ends per the drive manual and the drive chassis bonded; isolated instrument grounds only where a design requires them, still bonded.
- 9
Draw it
A grounding diagram showing every bar, every bond, the single points, the conductor sizes, and the site electrodes; the drawing in the panel set.
- 10
Verify
At commissioning: bond resistance from the enclosure and each bar to the supply ground in the milliohm range with a low-resistance ohmmeter; site electrode resistance with a ground tester and the value recorded; no voltage between the instrument bar and the enclosure with the plant running; every shield grounded at one end only.
| Ground | Purpose | Bonded to | Rule |
|---|---|---|---|
| Enclosure and equipment ground bar | Safety; fault clearing | Supply equipment grounding conductor | Everything metal; sized per the code |
| Control circuit ground | Fault clearing on 120 volt control | Enclosure at the transformer | One side of the secondary |
| Instrument ground bar | Reference for 24 volt common and shields | Enclosure at one point | Single bond; no fault current |
| Shield bar | Shield drains | Instrument bar | Shields grounded at the panel end only |
| Surge entrance bar | Surge current path | Enclosure ground and site electrodes | Shortest path; sized per the device |
| Site electrode system | Earth reference and lightning | Service, panel, mast, rods, steel | All bonded together |
Frequently asked questions
- Should the instrument ground have its own rod?
- No. A separate rod that is not bonded to the rest is an isolated ground and a hazard; the instrument ground is a bar bonded to the enclosure ground at one point. If a rod is installed for the instrument bar, it is bonded to the site electrode system too.
- Where do the cable shields go?
- On the shield bar at the panel end, with the field end insulated. A shield grounded at both ends carries ground loop current and noise into the signal.
- How low should the electrode resistance be?
- As low as the site allows, with the code and the surge device requirements as the reference; more important is that every electrode at the site is bonded together. Record the measured value and retest periodically.
- The drive manual says bond the motor cable shield at both ends. Does that contradict the shield rule?
- No. The drive output cable shield is a power circuit shield carrying high-frequency current back to the drive and is bonded at both ends per the drive manual. Signal shields are grounded at one end. Different circuits, different rules.
Related topics
- Ground Loops in InstrumentationTwo grounds at different potentials, one signal circuit between them, and a reading that will not sit still. How to find it and how to prevent it.
- Missing Equipment GroundAn enclosure, motor, or device with no effective equipment ground: how it shows up as a tingle, a fault that does not trip, surge protection that does nothing, or instrument noise; how to test the path safely; and why a ground rod is no substitute.
- Shield Grounded at Both EndsA shield connected to ground at the panel and again in the field becomes a conductor between two grounds, and its current becomes noise on the pair inside. How to find the second connection, what to measure before lifting it, and when both ends are correct.
- Panel Surge ProtectionSurge protection of a controller panel as a system: a single entrance and the ground bar it lands on, staged protection on the power, protectors on every loop and data line that leaves the building, the radio feed, layout, and the checklist after a strike.
- NFPA 70 and the Control PanelThe National Electrical Code inside an industrial control panel: Article 409 and the listing it points to, the short-circuit current rating, overcurrent protection for control circuits, grounding and bonding, working space, and what an inspector asks.
- How to Diagnose a Ground LoopProve that a noisy or offset analog signal is a ground loop, find the second ground, and fix it the right way: remove the extra ground, isolate the signal, or correct the shield termination. With the measurements that make the diagnosis certain.