Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceDocumentationPanelsEngineeringUL 508ADesign

Wiring Diagrams

The drawing that says where every wire goes: panel wiring and interconnection diagrams, and the conventions of wire numbers, conductor colors, terminal numbers, and cable numbers that make them readable. What belongs here versus on the schematic.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Wiring Diagrams

A wiring diagram shows the physical connections of a control system: each terminal strip with its numbered terminals, each device with its terminal designations, and each wire with its number, color, and size running between them, plus the cables that leave the panel with their numbers and the terminals they land on at the far end. It complements the schematic, which shows how a circuit works, by showing where the wires run, and the two are tied together by wire numbers that appear on both. Conventions for wire numbering, conductor colors by voltage class, terminal numbering, and cable numbering are set in the project standard and followed on every sheet, and the diagram is marked up during construction and issued as a record drawing so that the panel and the paper agree for the life of the system.

Key points

  • The schematic says how it works; the wiring diagram says where the wires go. Wire numbers tie them together.
  • One convention for wire numbers, one for colors, one for terminals, one for cables, applied on every sheet.
  • Conductor colors follow the industrial standard by voltage class, so a red wire is AC control and a blue wire is DC control on every panel.
  • Interconnection diagrams carry the field cables: cable number, conductors, and the terminal at each end.
  • Shield terminations, grounds, and spare conductors are drawn, not assumed.
  • Construction markups become the record drawing; a wiring diagram that was never updated is fiction.

What it shows

Panel wiring diagram
The terminal strips, devices, and internal wiring of one panel, drawn so that a wireman can build it and a technician can trace it. Terminal numbers, wire numbers, colors, sizes, and the device terminals they land on.
Interconnection diagram
The cables between panels and between panels and field devices: each cable with its number and type, each conductor with its color or number, the terminal at each end, shields and their termination point. The bridge between the panel drawings and the field.
Loop diagram
One instrument loop from the transmitter to the controller input, through every junction box and terminal, with power, shield, and grounding shown; the instrument society standard defines the format.
Terminal diagram
A listing view of one terminal strip: terminal number, internal wire, external cable and conductor, and the destination of each, often generated from the wiring database.

Wire numbers

Every wire carries a number, and the number is what a technician reads on the wire label and finds on the drawing. The common conventions are numbering by the schematic line where the wire originates, so that wire 105 comes from line 105 and every wire connected to it electrically carries the same number, and sequential numbering by circuit or by terminal strip. The line-number method is the most traceable: a technician who finds wire 105 on a terminal opens the schematic to line 105. Whichever is chosen, a wire keeps its number through every terminal it passes, a wire that passes through a contact changes number on the other side, and the number is on the wire at both ends and on every drawing that shows it.

Conductor colors

ColorUseNote
BlackUngrounded line, load, and control conductors at line voltagePower wiring
RedUngrounded AC control conductors at less than line voltageControl transformer secondary circuits
BlueUngrounded DC control conductorsTwenty-four volt control and I/O
Yellow, or orange by some standardsCircuits that remain energized when the main disconnect is open, fed from an external sourceInterlocks from other panels; a warning to whoever opens the panel
White, or grayGrounded AC conductor, the neutralNever used for anything else
White with blue stripeGrounded DC conductor, the DC commonDistinguishes the DC common from the AC neutral
Green, or green with yellow stripeEquipment grounding conductorNever used for anything else
The convention used in the industrial machinery and industrial control panel standards; the project standard states it

Colors let a technician know the voltage class of a wire before reading its number, and the yellow convention in particular has prevented shocks from interlock circuits that stayed live with the panel disconnect open. The wiring diagram states the color of every wire, or states the convention once and the exceptions individually. Field cables with numbered or colored conductors are identified on the interconnection diagram by the conductor number or color inside the cable, which is different from the panel convention and is stated as such.

Terminals and cables

  • Terminal strips are named and terminals numbered in the order they are mounted, with the strip name and number on the drawing and on the strip. A terminal is shown once, with everything that lands on it.
  • Field cables are numbered by a convention that encodes the origin, the destination, or the loop: the cable schedule holds the list, and the interconnection diagram shows each cable by number with its conductors.
  • Shields are drawn as a conductor that lands on a shield terminal or a ground bar at one end and is shown cut back and insulated at the other. A shield that is not drawn is a shield that will be grounded at both ends.
  • Spare conductors are shown landed on spare terminals or coiled and labeled, so that the record says they exist.
  • Ground bars and the equipment ground conductor are drawn with their connections, including the bonding of the door and the back plate.

Reading one under pressure

  1. 1

    Start from the schematic

    Find the circuit that is not working and the wire number where it fails.

  2. 2

    Find the wire on the wiring diagram

    Its terminal, its device terminal, and its color. The wiring diagram index lists wire numbers by sheet.

  3. 3

    Follow it to the field

    The interconnection diagram gives the cable and conductor that carries it, and the terminal at the far end.

  4. 4

    Check the physical against the paper

    The wire label, the terminal number, the cable tag. Where they disagree, the paper is wrong or the wire was moved, and either is a finding.

Keeping it true

During construction the panel builder marks changes on a set of drawings, and the field electrician does the same for the interconnection diagrams. At the end of commissioning those markups are incorporated into a record set, issued as as-built, and that set is what the utility keeps. Every change after that is a change record that includes the drawing revision. A utility that keeps its wiring diagrams true can send a technician to any panel with confidence; one that does not has drawings that are consulted once, found wrong, and never opened again.

Frequently asked questions

Do we need both a schematic and a wiring diagram?
Yes, for anything beyond a trivial panel. The schematic shows function and is what is read to understand and troubleshoot a circuit; the wiring diagram shows connections and is what is read to build and trace it. Combining them produces a drawing that does neither job well.
Which wire numbering method should we use?
Numbering by schematic line is the most traceable and is the common practice in North American industrial panels. The important thing is one method across the project, stated in the standard, and used by every panel builder and integrator on the job.
The panel builder used different colors from our standard. Does it matter?
It matters for safety and for every technician who opens the panel expecting the standard. The colors are in the specification and are checked at the factory acceptance test; a panel that arrives with the wrong colors is corrected or the drawings state the deviation prominently. Yellow for externally fed circuits is not negotiable.
Where do loop diagrams fit?
A loop diagram is a wiring diagram for one instrument loop, showing every connection from the field device to the controller channel across junction boxes and panels, with power, shield, and grounding. Plants with many instruments produce one per loop from the instrument database; smaller systems cover the same information on the interconnection diagram and the I/O list.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.