Water and Wastewater Utility Threat Landscape

What has actually happened at water utilities, what those incidents had in common, and the small number of controls that would have prevented most of them.

8 min readUpdated Aug 28, 2026Published Jul 7, 2026By Eric Sullivan

The short answer

Water and Wastewater Utility Threat Landscape

Publicly reported incidents at water and wastewater utilities have overwhelmingly involved internet-exposed remote access, default or shared credentials, and unsupported software rather than sophisticated attacks. Small utilities are disproportionately affected because they have the same exposed technology as large ones with far less staff. The controls that address most of this are unglamorous: remove internet exposure, replace default credentials, segment, and test backups.

Key points

  • Most reported incidents traced to exposed remote access and weak credentials.
  • Small systems face the same exposure with a fraction of the staff.
  • Internet-reachable HMIs and controllers are found routinely on public scanning services.
  • CISA, EPA, and AWWA publish free sector guidance and assessments.
  • Manual operation procedures are a real and often overlooked control.

What the reported incidents have in common

Across publicly reported water sector incidents, a consistent pattern emerges, and it is not the one people expect. These have rarely been sophisticated campaigns against hardened targets. They have been opportunistic access to systems that were reachable from the internet and protected by credentials that were default, shared, or previously breached.

  • Remote access reachable from the internet, often a remote desktop service or an HMI web interface.
  • Default vendor credentials still in place, or a single shared password known to many people including former staff.
  • No multi-factor authentication on any remote path.
  • Flat networks where reaching one device meant reaching everything.
  • Unsupported operating systems with no compensating controls around them.
  • No monitoring, so intrusions were discovered by an outside party or by operators noticing odd equipment behavior.

Why small utilities are disproportionately exposed

A system serving three thousand people runs the same PLCs, the same SCADA software, and the same cellular RTUs as one serving three hundred thousand. What differs is staff. A small utility may have no dedicated IT person, let alone anyone whose job includes OT security, and the integrator who built the system may be the only one who has ever logged into it.

That is why sector guidance emphasizes a short list of high-value actions rather than a comprehensive program. A small utility that does five things well is enormously better off than one that starts a framework it cannot staff.

The short list

  1. 01Find and remove internet exposure. Inventory every device with a public path and eliminate it. Remote access should terminate at a VPN or a broker with multi-factor authentication, never directly on an HMI or a controller.
  2. 02Replace default and shared credentials. Inventory every account on every device, including the ones inside panels. Remove accounts belonging to people who have left.
  3. 03Require multi-factor authentication on all remote access, including vendor access.
  4. 04Segment the control network from everything else, with a controlled boundary and no direct path from business systems to controllers.
  5. 05Back up controller programs, HMI applications, and server images. Keep a copy offline. Restore one on a bench so you know it works.
  6. 06Write and practice manual operation procedures, so the plant can run if the control system is unavailable.
  7. 07Know who to call. Have contact information for your integrator, your state regulator, and the federal reporting path written down somewhere that does not depend on the network.

Where to get help

CISA
Publishes advisories, free vulnerability scanning services, and sector-specific guidance for water and wastewater. The advisories are worth subscribing to because they name the specific equipment affected.
EPA
Provides cybersecurity guidance, assessment tools, and technical assistance for drinking water and wastewater systems.
AWWA
Publishes water sector cybersecurity guidance and an assessment tool aligned to sector needs.
WaterISAC
Sector information sharing, including threat notifications relevant to water and wastewater utilities.
State primacy agency
Often has technical assistance programs and, increasingly, expectations about cybersecurity as part of sanitary surveys.

AWIA requires community water systems above a certain population served to conduct risk and resilience assessments and to maintain emergency response plans, and cybersecurity is part of that scope. Confirm the current requirements and deadlines applicable to your system with your primacy agency rather than relying on a summary.

Frequently asked questions

Are small water systems really targeted?
Most reported incidents were not targeting a specific utility. They were opportunistic access to whatever was reachable and weakly protected. Being small offers no protection when the exposure is discoverable by automated scanning.
What is the single highest-value thing to do first?
Eliminate direct internet exposure of control systems, and put multi-factor authentication on every remote access path. That combination addresses the initial access method in the large majority of publicly reported water sector incidents.
Does cyber insurance cover a control system incident?
It depends entirely on the policy, and many policies have requirements or exclusions relating to remote access controls and multi-factor authentication. Read the policy with your broker before you need it.
Do we have to report an incident?
Reporting obligations vary by state, by system type, and by federal rule, and they have been changing. Confirm the current requirement with your state primacy agency and have the reporting path written down before an incident, not during one.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.