The short answer
AWIA Requirements
Section 2013 of the America's Water Infrastructure Act of 2018 amended the Safe Drinking Water Act to require every community water system serving more than 3,300 people to conduct a risk and resilience assessment and to prepare or revise an emergency response plan based on it, and to certify completion of each to the federal environmental agency by deadlines set by population served, with the cycle repeating every five years. The assessment must consider malevolent acts and natural hazards to the system's physical and electronic assets, explicitly including its electronic, computer, and automated systems such as SCADA, along with source water, treatment, storage, distribution, monitoring, chemicals, and finances; the plan must include resilience strategies for physical security and cybersecurity, response procedures, mitigation actions, and detection strategies. The utility certifies that the work was done rather than submitting the documents, keeps them protected, and uses its control system security program to supply the cybersecurity portions.
Key points
- Covered: community water systems serving more than 3,300 people; wastewater-only utilities are not covered by this section.
- Two deliverables: a risk and resilience assessment, then an emergency response plan within six months of it.
- Deadlines by population band, and the cycle repeats every five years from the original certification dates.
- Cybersecurity is a named element of both: the assessment covers the electronic and automated systems, the plan covers cyber resilience and response.
- Certification, not submission: the utility certifies to the agency that the work was done, and keeps the documents secure.
- The control system security program is where the cyber content comes from; the assessment is the place it gets written down.
Who is covered and when
| Population served | First risk and resilience assessment certification | First emergency response plan certification | Cycle |
|---|---|---|---|
| 100,000 or more | March 31, 2020 | September 30, 2020 | Every five years from those dates: 2025 and 2030 for the assessment |
| 50,000 to 99,999 | December 31, 2020 | June 30, 2021 | December 2025 and June 2026, then 2030 and 2031 |
| 3,301 to 49,999 | June 30, 2021 | December 31, 2021 | June 2026 and December 2026, then 2031 |
| 3,300 or fewer | Not required by this section | Not required by this section | State requirements may apply; the practices are still recommended |
The requirement applies to community water systems, the systems that serve the same people year round. Wastewater utilities and non-community systems are not covered by this section, although other rules and state requirements may reach them, and the practices apply to them just as well. A utility that operates both water and wastewater assesses the water system under the act and is well advised to include the wastewater system in the same work.
What the assessment must include
- The risk to the system from malevolent acts and natural hazards.
- The resilience of the pipes and constructed conveyances, physical barriers, source water, water collection and intake, pretreatment, treatment, storage and distribution facilities.
- The electronic, computer, or other automated systems, including the security of such systems, which is the SCADA, the controllers, the networks, and the business systems that the utility depends on.
- The monitoring practices of the system.
- The financial infrastructure.
- The use, storage, or handling of chemicals.
- The operation and maintenance of the system.
- Optionally, an evaluation of capital and operational needs for risk management and resilience.
What the plan must include
- Strategies and resources to improve the resilience of the system, including the physical security and cybersecurity of the system.
- Plans and procedures that can be implemented, and identification of equipment that can be utilized, in the event of a malevolent act or natural hazard that threatens the ability to deliver safe drinking water.
- Actions, procedures, and equipment that can obviate or significantly lessen the impact of such an event on public health and the safety and supply of drinking water, including the development of alternative source water options, relocation of intakes, and construction of flood protection barriers.
- Strategies that can be used to aid in the detection of malevolent acts or natural hazards that threaten the security or resilience of the system.
Where the cyber content comes from
The assessment asks the utility to evaluate the security of its automated systems and the plan asks for cyber resilience, response, and detection strategies. A utility with a control system security program has the answers already: the asset inventory says what the automated systems are, the risk assessment ranks what could happen to them, the baseline controls are the resilience strategies, the incident response plan and the manual operation procedures are the response plans, and change detection and monitoring are the detection strategies. The act does not prescribe a method for the cyber portion; the sector guidance points to the federal cybersecurity performance goals, the sector cybersecurity checklists, and the industrial security standards, and the utility uses whichever it has adopted and documents the result in the assessment.
Tools and methods
- The federal agency assessment tool
- A free software tool built for the requirement that walks a utility through the assets, threats, consequences, vulnerabilities, and countermeasures, and produces the documentation.
- The sector risk analysis standard
- The water sector standard for risk and resilience management of water and wastewater systems, which many utilities and consultants use as the method behind the assessment.
- The federal cybersecurity checklist for water utilities
- A checklist aligned with the cross-sector performance goals that produces the cyber findings for the assessment.
- Consultants
- Many utilities engage a consultant for the assessment, particularly the first one; the utility still owns the result and must be able to explain it.
Certification
- 1
Complete the assessment
With the cyber portion drawn from the security program and documented in the assessment.
- 2
Certify
Through the federal agency online portal or by the alternative means it provides, by the deadline for the population band. The certification says the assessment was conducted; the document itself is not submitted.
- 3
Prepare or revise the plan
Within six months of the assessment certification, based on its findings.
- 4
Certify the plan
By the plan deadline, the same way.
- 5
Protect the documents
Both documents contain the vulnerabilities of the system; they are kept with the security documentation, with access limited and copies controlled. The act provides some protection from public disclosure; state records laws vary.
- 6
Use them
The findings become the security program plan for the next five years, and the emergency response plan is exercised. A plan written for certification and shelved has met the letter of the law and nothing else.
- 7
Repeat
Every five years, with the assessment reviewed and revised rather than started from scratch, and the cyber portion updated from the current state of the program.
Frequently asked questions
- We serve 3,000 people. Are we exempt from everything?
- From the certification requirement of this section, yes. Not from the threats, and possibly not from state requirements or from federal enforcement under the broader emergency powers of the drinking water law. The same assessment and plan, scaled down, are recommended for every system, and free help is available for small ones.
- Does the assessment have to be done by a certified professional?
- No. The act requires the utility to conduct it and certify that it did; it does not require a particular credential. Many utilities use consultants for the method and the documentation; the utility signs the certification.
- Is the assessment a public record?
- The act directs the federal agency to protect the information from disclosure, and the certification the agency receives contains no details. Copies held by the utility are subject to state public records laws, which often have exemptions for security-sensitive information; the utility should confirm with counsel and mark the documents accordingly.
- What happens if we miss the deadline?
- The federal environmental agency has enforcement authority under the drinking water law, and it has used it. Late is better than never: complete the work, certify, and document why it was late. The greater risk is the one the assessment would have found.
Related topics
- EPA GuidanceWhat the federal environmental agency provides to water and wastewater utilities on cybersecurity and what it expects: the free assessment, the checklist aligned with federal goals, joint incident response guidance, the enforcement position, and how to use it.
- CISA ResourcesWhat the federal cybersecurity agency provides to utilities without charge: the performance goals, regional advisors, external vulnerability scanning, control system advisories, the exploited catalog, a self-assessment tool, exercises, and incident reporting.
- OT Risk AssessmentRanking what could go wrong in a control system and what it would cost: the consequence-first method for utilities, the assets and scenarios to list, likelihood without pretending to know it, the risk matrix, and turning the ranked list into a work plan.
- OT Incident Response PlanThe plan for the day the control system is not trusted: who decides, the triggers, the first hour, isolating without stopping treatment, running by hand, preserving evidence, who to notify and when, recovery from backups, and the exercise that makes it real.
- Security Program BasicsWhat a control system security program is for a utility that has never had one: a named owner, an inventory, a risk assessment, a few policies, baseline controls, training, vendor rules, an exercised incident plan, and a first-year plan for a small staff.
- Small Utility Cybersecurity PrioritiesWhat a utility with a few operators and no IT department should do first: the ten measures that remove most of the risk for the least money and time, in the order to do them, with what each one costs, what it prevents, and how to know it is done.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.