The short answer
Lost Communications
A lost communication event is diagnosed by its scope: one device, one site, every site on one channel or medium, or everything, and each scope points to a different layer. One device is its cable, port, address, or the device itself; one site is its radio, modem, power, or controller; one channel is the master radio, the cellular carrier, or the server driver for that channel; everything is the server, its network connection, the firewall, or the core switch. The system should respond to any of them by raising a communication alarm, marking the affected data bad, showing the status on the displays, and letting the site run on local control while remote controllers buffer their history, and the diagnosis works outward from the server with the driver statistics, the network tools, the radio or modem diagnostics, and finally the site.
Key points
- Scope first: one device, one site, one channel, or everything. Each scope has its own short list.
- The server driver statistics say when the last good response was and what failed; start there.
- Work outward: server, network, firewall, medium, remote controller, device.
- A lost link must raise an alarm and mark data bad; a lost link that looks like a stable site is the failure to design out.
- The site runs on local control while the link is down; the design says how, and the commissioning tested it.
- Two paths for the sites that cannot afford to be lost, and store and forward for the history.
What should happen
Communication is lost regularly in any system with remote sites, and the measure of a good design is that the loss is an alarm and nothing worse. The server declares the device offline after its timeout and retries, raises a communication alarm at the priority the philosophy assigns, marks every tag from the device bad, and the displays show the status and replace the values with bad-quality markers. Alarms from the site that depend on the lost data are suppressed by the parent communication alarm so that one event produces one alarm. At the site, the controller continues on local control: the wet well is pumped on level, the pressure is held on the local transmitter, chemical feed follows local flow, and the history is buffered for delivery when the link returns. When the link returns, the tags go good, the buffered history is backfilled, and the alarm clears. Any part of that which does not happen is a finding for the design, separate from the cause of the loss.
Scope tells the story
| Scope | Likely causes | First checks |
|---|---|---|
| One device at a site | Its cable, switch port, address, a device reset or fault, a changed configuration | Other devices at the site are fine; ping the device from the site controller; the device display |
| One site | Site power, radio or modem, antenna and coax, the site controller stopped, a lightning event | Radio or modem status if reachable; power fail alarm if it arrived; other sites on the same channel fine |
| All sites on one radio channel | Master radio, its antenna, its power, or the server serial or Ethernet port for that channel; interference on the channel | Master radio indicators; the server driver for the channel; other channels fine |
| All cellular sites | Carrier outage, VPN concentrator, private network gateway, an expired certificate or account | Carrier status; the VPN server; one modem checked directly |
| All sites and the plant | The server itself, its network interface, the core switch, the firewall, a driver or license failure | Server driver status; ping from the server to a plant controller; firewall and switch status |
| Intermittent, many sites | Poll cycle too long for the timeout, a radio path degrading, a noisy channel, an overloaded server | Success rates and response times per site over time; the ones getting worse |
Working outward
- 1
Server
Driver diagnostics: which devices are offline, since when, the error counts, and the last good response time. Service status and license status. The server network interface and its link.
- 2
Network
Ping from the server to the gateway, to the firewall, to a plant controller, to the master radio or the VPN gateway. Switch port status for the server and the radio.
- 3
Firewall
Rules unchanged; logs for denied traffic on the polling ports; VPN tunnels up.
- 4
Medium
Master radio: power, status, signal, transmit indication. Cellular: the VPN gateway, the carrier, one modem reached directly. Leased line: the circuit status from the carrier.
- 5
Remote site
Power and generator status if any alarm arrived before the loss; the radio or modem, antenna, and coax; the site controller running; the site switch.
- 6
Device
Cable, port, address, configuration, and the device itself.
Tools
- Driver statistics and the communication diagnostic display in the SCADA.
- Ping and traceroute from the server and from a laptop at the site.
- Radio diagnostics: received signal strength, signal-to-noise ratio, packet error rate, at both ends, compared with the commissioning record.
- Cellular modem status pages: signal, registration, IP address, VPN state, data usage.
- Firewall logs and VPN concentrator status.
- The site controller online: is it running, what does its communication module report.
- A protocol test tool to poll a device directly, bypassing the server, to separate the device from the server.
Designing for loss
- Local control at every site that does not need the link to keep the process safe, tested by disconnecting the link.
- Timeouts and retries that declare loss promptly, and quality that goes bad when they do.
- Communication alarms with priority, and parent-child suppression of the site alarms that follow.
- Store and forward in the remote controller for the history that the utility needs continuous.
- A second path for sites whose loss is a public health or overflow risk.
- Diagnostics historized and alarmed on degradation, so that the path is fixed before it fails.
Frequently asked questions
- How long should the server wait before declaring a site lost?
- Longer than the worst normal poll cycle including retries, and shorter than the time in which the loss matters. On a radio channel with a 20-second cycle, a minute or two is common; on plant Ethernet, seconds. The alarm delay can be longer than the quality change: mark the data bad at the first failure and alarm after a short confirmation.
- The site is lost but its power fail alarm never arrived. Is that possible?
- Yes: if the power failed and the radio lost power at the same instant, nothing was sent. A UPS on the radio and the controller, sized for a few minutes, lets the site report the power failure before it goes dark, which is worth the cost of the UPS for the information alone.
- Everything went down at once. Where do I look first?
- At the server and its immediate network: the driver services, the network interface, the switch port, and the firewall. A single point that takes everything down is almost always within a few feet of the server, or is the server itself. Check whether the plant controllers on the local network are also lost; if they are, it is not the radios.
- Should lost communication stop the pumps at a remote site?
- No. The site controller runs the process on local measurements, and losing the link changes nothing at the site except that the operator cannot see it. A site that stops when the link fails has a design problem; a site that needs the link for its setpoints holds the last ones or reverts to a local default.
Related topics
- SCADA CommunicationsHow SCADA servers talk to controllers and the field: polling and report by exception, the protocols and what each is for, media from plant Ethernet to radio and cellular, poll rate arithmetic, timeouts and quality, time sync, store and forward, and security.
- Device Times OutA polled device that answers late or not at all: how to read the driver counters, tell a dead device from a slow one, and find the timeout setting, the bus loading, the radio latency, the duplicate address, or the device that is simply too busy to answer.
- Ethernet Device Drops OfflineAn industrial Ethernet device that disappears and comes back. Duplex mismatch, cabling, spanning tree, and the switch counters that identify it in minutes.
- Bad QualityWhat a quality flag means and where it comes from: good, uncertain, and bad with substatus codes, how quality propagates from device through driver, tag, display, alarm, and historian, the causes by layer, and the rule that a bad value is never a number.
- Lift Station Backup ControlHow a lift station keeps pumping when the transmitter, the PLC, or the SCADA link is gone: float backup logic, the control transfer relay, redundant-off protection, and how to test it with the controller actually dead.
- How to Diagnose Packet LossFind where and why frames are dropped: measure loss with a continuous ping, localize it hop by hop from both directions, read the port counters on the path, and match the pattern to its cause: a cable, a duplex mismatch, congestion, a loop, or a radio link.