Lost Communications

What should happen when SCADA loses a device, a site, or everything, how the pattern tells which, the diagnostic order from the server outward through network, firewall, medium, and site, and the design that makes a lost link an alarm rather than an incident.

9 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Lost Communications

A lost communication event is diagnosed by its scope: one device, one site, every site on one channel or medium, or everything, and each scope points to a different layer. One device is its cable, port, address, or the device itself; one site is its radio, modem, power, or controller; one channel is the master radio, the cellular carrier, or the server driver for that channel; everything is the server, its network connection, the firewall, or the core switch. The system should respond to any of them by raising a communication alarm, marking the affected data bad, showing the status on the displays, and letting the site run on local control while remote controllers buffer their history, and the diagnosis works outward from the server with the driver statistics, the network tools, the radio or modem diagnostics, and finally the site.

Key points

  • Scope first: one device, one site, one channel, or everything. Each scope has its own short list.
  • The server driver statistics say when the last good response was and what failed; start there.
  • Work outward: server, network, firewall, medium, remote controller, device.
  • A lost link must raise an alarm and mark data bad; a lost link that looks like a stable site is the failure to design out.
  • The site runs on local control while the link is down; the design says how, and the commissioning tested it.
  • Two paths for the sites that cannot afford to be lost, and store and forward for the history.

What should happen

Communication is lost regularly in any system with remote sites, and the measure of a good design is that the loss is an alarm and nothing worse. The server declares the device offline after its timeout and retries, raises a communication alarm at the priority the philosophy assigns, marks every tag from the device bad, and the displays show the status and replace the values with bad-quality markers. Alarms from the site that depend on the lost data are suppressed by the parent communication alarm so that one event produces one alarm. At the site, the controller continues on local control: the wet well is pumped on level, the pressure is held on the local transmitter, chemical feed follows local flow, and the history is buffered for delivery when the link returns. When the link returns, the tags go good, the buffered history is backfilled, and the alarm clears. Any part of that which does not happen is a finding for the design, separate from the cause of the loss.

Scope tells the story

ScopeLikely causesFirst checks
One device at a siteIts cable, switch port, address, a device reset or fault, a changed configurationOther devices at the site are fine; ping the device from the site controller; the device display
One siteSite power, radio or modem, antenna and coax, the site controller stopped, a lightning eventRadio or modem status if reachable; power fail alarm if it arrived; other sites on the same channel fine
All sites on one radio channelMaster radio, its antenna, its power, or the server serial or Ethernet port for that channel; interference on the channelMaster radio indicators; the server driver for the channel; other channels fine
All cellular sitesCarrier outage, VPN concentrator, private network gateway, an expired certificate or accountCarrier status; the VPN server; one modem checked directly
All sites and the plantThe server itself, its network interface, the core switch, the firewall, a driver or license failureServer driver status; ping from the server to a plant controller; firewall and switch status
Intermittent, many sitesPoll cycle too long for the timeout, a radio path degrading, a noisy channel, an overloaded serverSuccess rates and response times per site over time; the ones getting worse

Working outward

  1. 1

    Server

    Driver diagnostics: which devices are offline, since when, the error counts, and the last good response time. Service status and license status. The server network interface and its link.

  2. 2

    Network

    Ping from the server to the gateway, to the firewall, to a plant controller, to the master radio or the VPN gateway. Switch port status for the server and the radio.

  3. 3

    Firewall

    Rules unchanged; logs for denied traffic on the polling ports; VPN tunnels up.

  4. 4

    Medium

    Master radio: power, status, signal, transmit indication. Cellular: the VPN gateway, the carrier, one modem reached directly. Leased line: the circuit status from the carrier.

  5. 5

    Remote site

    Power and generator status if any alarm arrived before the loss; the radio or modem, antenna, and coax; the site controller running; the site switch.

  6. 6

    Device

    Cable, port, address, configuration, and the device itself.

Tools

  • Driver statistics and the communication diagnostic display in the SCADA.
  • Ping and traceroute from the server and from a laptop at the site.
  • Radio diagnostics: received signal strength, signal-to-noise ratio, packet error rate, at both ends, compared with the commissioning record.
  • Cellular modem status pages: signal, registration, IP address, VPN state, data usage.
  • Firewall logs and VPN concentrator status.
  • The site controller online: is it running, what does its communication module report.
  • A protocol test tool to poll a device directly, bypassing the server, to separate the device from the server.

Designing for loss

  • Local control at every site that does not need the link to keep the process safe, tested by disconnecting the link.
  • Timeouts and retries that declare loss promptly, and quality that goes bad when they do.
  • Communication alarms with priority, and parent-child suppression of the site alarms that follow.
  • Store and forward in the remote controller for the history that the utility needs continuous.
  • A second path for sites whose loss is a public health or overflow risk.
  • Diagnostics historized and alarmed on degradation, so that the path is fixed before it fails.

Frequently asked questions

How long should the server wait before declaring a site lost?
Longer than the worst normal poll cycle including retries, and shorter than the time in which the loss matters. On a radio channel with a 20-second cycle, a minute or two is common; on plant Ethernet, seconds. The alarm delay can be longer than the quality change: mark the data bad at the first failure and alarm after a short confirmation.
The site is lost but its power fail alarm never arrived. Is that possible?
Yes: if the power failed and the radio lost power at the same instant, nothing was sent. A UPS on the radio and the controller, sized for a few minutes, lets the site report the power failure before it goes dark, which is worth the cost of the UPS for the information alone.
Everything went down at once. Where do I look first?
At the server and its immediate network: the driver services, the network interface, the switch port, and the firewall. A single point that takes everything down is almost always within a few feet of the server, or is the server itself. Check whether the plant controllers on the local network are also lost; if they are, it is not the radios.
Should lost communication stop the pumps at a remote site?
No. The site controller runs the process on local measurements, and losing the link changes nothing at the site except that the operator cannot see it. A site that stops when the link fails has a design problem; a site that needs the link for its setpoints holds the last ones or reverts to a local default.