The short answer
SCADA Clients
A SCADA client is the software and the screen through which an operator watches and controls the process. Thick clients run the full runtime on a workstation and are the control room standard; thin and web clients render displays served by a server and cost less to deploy and maintain; mobile clients give supervisors and on-call staff a view and limited acknowledgment. Every client authenticates a user with a role that decides what can be seen and what can be commanded, control is permitted only from clients in the control room or a defined location, operator workstations are dedicated and locked down, sessions time out, and clients are configured to follow a redundant server pair automatically. The count and type of clients is a licensing and a security decision as much as a convenience.
Key points
- Thick client for the control room, web client for everywhere else, mobile for view and acknowledgment only.
- A user, a role, and a location decide what a client can do; control from outside the control room needs a deliberate exception.
- Operator workstations are dedicated to SCADA: no email, no browsing, kiosk mode, no local administrator.
- Individual logins with a shared operator view; a shift change is a login, and the audit trail shows who did what.
- Clients follow the redundant pair automatically, and the operator is told which server is active.
- Every client is a license and an attack surface; count both.
Client types
| Type | How it works | Best for | Watch out for |
|---|---|---|---|
| Thick client | The full SCADA runtime installed on a workstation, connected to the servers | Control room operator stations; full performance, full control | Software to install, patch, and license on every machine |
| Thin client | A terminal that displays a session running on a server | Plant floor and office stations where nothing should be installed locally | Server load per session; the terminal server is a critical machine |
| Web client | A browser renders displays served by a web server | Supervisors, offices, remote view, mobile devices | Browser security; which functions the web client is allowed; the web server sits in a DMZ when exposed |
| Mobile app | A vendor app or a mobile-formatted web display | On-call staff: view, alarm acknowledgment, notification | Control from a phone is a policy question with a default answer of no |
| Panel HMI | A local operator interface on a panel, sometimes a SCADA client, sometimes its own device | Local operation at the equipment | Consistency with the SCADA displays; who can do what from the panel |
Users, roles, and location
Every client session belongs to a logged-in user with a role. A viewer sees and cannot command. An operator commands the equipment the role covers. A supervisor changes setpoints outside operator limits, shelves alarms, and bypasses permissives. An engineer changes configuration. Those roles are defined once in the philosophy and applied by the platform. The location of the client is a second dimension: a control room client with an operator logged in can command; the same operator on a web client in a truck should not, unless the utility has decided that remote operation is acceptable, in which case the conditions are written down. Most platforms can restrict control by client station as well as by user, and both should be used.
The operator workstation
- Dedicated to SCADA: no email, no web browsing, no document editing. A workstation that does other things gets malware from other things.
- Locked down: the operator account cannot install software, change network settings, or reach the file system; the SCADA client starts at boot and fills the screens; a kiosk configuration.
- Individual logins: each operator logs in with their own credentials at shift change, so the audit trail names a person. A shared operator account defeats the audit trail and the incident investigation.
- Screens: two to four monitors arranged by the display hierarchy, with the overview always visible and alarms always visible, at a size and distance that the text is readable from the chair.
- Hardware: a business-class or industrial workstation on the UPS, with spares, and a replacement plan; a client that fails on a Sunday night should be replaceable by the operator with a spare and a checklist.
- Audible alarm: a horn or a speaker driven by the client or by a separate annunciator, with the acknowledgment on the client.
Sessions and failover
Sessions time out after inactivity, to a view-only state rather than a logout in the control room, so that a screen is never left commanding under a departed operator and a returning operator is never locked out of the overview. Clients are configured with both servers of a redundant pair and switch automatically when the active server fails; the operator sees a brief indication and the displays continue. The switch is tested as part of the failover test, from every client type, because a thick client that follows and a web client that hangs is a common finding. Display of which server is active belongs on every client.
Licensing and count
Clients are licensed by concurrent connection, by named installation, or by type, and the count is easy to exceed when web clients are cheap to add. The count is also a security decision: every client is a machine that can reach the SCADA servers, and a web client in a manager office extends the SCADA network into the office. Decide who needs a client, of which type, with which role and from where, write it down, and revisit it when someone asks for one more.
Frequently asked questions
- Should operators have individual logins or a shared operator account?
- Individual logins. The audit trail, the alarm acknowledgment record, and the incident investigation all depend on knowing who was at the console. A shared account is convenient for exactly as long as nothing goes wrong. Make the login quick, with a badge or a short credential, and make the session time out to view-only rather than locking the screen.
- Is a web client as good as a thick client?
- For viewing and for many operator functions on modern platforms, yes. For the control room, a thick client still gives the most predictable performance, the most complete function set, and the fewest dependencies. Use the thick client where control happens and web clients everywhere else.
- Can an on-call operator control from a phone?
- The platform can allow it; the question is whether the utility should. Acknowledging an alarm and viewing the system from a phone is reasonable. Starting a pump from a phone at 3 a.m., with no view of the site and a screen the size of a hand, is a risk the utility must consciously accept, in writing, with the conditions. Most do not.
- What happens on the client when the server fails over?
- A correctly configured client reconnects to the standby within seconds, shows a message, and continues with the same displays; alarm states and acknowledgments carry over on platforms that synchronize them. A client that shows stale data with no indication is the dangerous case; every platform can show communication status on the display, and it should be on every one.
Related topics
- SCADA ServersWhat the servers in a SCADA system do and what a utility should expect of them: the I/O, alarm, historian, and client roles, physical versus virtual, redundancy, sizing, placement, backup, patching, licensing, and monitoring.
- SCADA RedundancyWhat redundant SCADA servers protect against and what they do not, how failover works for tags, alarms, history, and clients, the network and controller layers beneath it, and why an untested failover is not redundancy.
- HMI NavigationHow operators move through the displays: the display hierarchy from overview to detail, a fixed navigation bar with area alarm indication, one-click paths from an alarm to the device, the rules that keep any display within two clicks, and what to leave out.
- Jump HostsThe one machine every remote session must pass through: what a jump host is, how it is hardened, what it may reach, session recording, the tools it carries, and why a vendor laptop never gets past it.
- Default CredentialsThe passwords printed in the manual: where they hide in a control system, why they are the first thing an attacker tries, how to find every one on site, and the procedure for changing them without locking yourself out.
- High Performance HMI DesignGrey backgrounds, reserved color, and displays designed to make abnormal conditions obvious rather than to look impressive in a demo.