The short answer
HMI Faceplates
A faceplate is the pop-up window that opens when an operator selects a device on a process display. It shows that device state, mode, setpoints, and diagnostics, and it carries the commands the operator may give. Good faceplates are built once per device type from a standard object, laid out identically, show why a device is not doing what it was told, and expose commands according to the user role. The process display shows the situation; the faceplate is where the operator acts.
Key points
- One faceplate design per device type, instantiated for every device. Consistency is the feature.
- Show the mode, the command, the feedback, and the disagreement between them.
- Show the interlocks and permissives by name, with the one that is holding the device highlighted.
- Commands respect the user role and confirm anything with consequences.
- Everything on the faceplate comes from the controller. The faceplate does not contain logic.
What a faceplate is for
A process display is built to show the state of the process at a glance, and ISA-101 practice keeps it uncluttered: a pump is a symbol with a status, not a panel of buttons. When the operator needs to act on that pump, or to see why it is not running, they select it and a faceplate opens. The faceplate is the detailed view and the control surface for one device. It holds everything the display leaves out.
Because it is opened for one device at a time and every device of a type gets the same one, the faceplate is where consistency pays off most. An operator who has learned the pump faceplate has learned every pump in the plant. That is achievable only if the faceplate is built once, as a standard object tied to a standard controller block, and never customized per device.
What a pump faceplate shows
| Element | Content | Note |
|---|---|---|
| Header | Tag, description, and a navigation link to the process display it lives on | Same position on every faceplate |
| Mode | Hand, Off, Auto from the local HOA; Manual or Auto in the controller; Local or Remote where the device has it | Show what the physical switch says and what the controller is doing; they are not the same thing |
| Command and feedback | Commanded state, running feedback, and a visible disagreement indicator when they differ beyond the proof time | The disagreement is the diagnostic operators use most |
| Process values | Speed reference and actual speed, motor current, run hours, starts today | Numbers with units, and a trend link on each |
| Interlocks and permissives | Each by name, with status, and the first one that is holding the device highlighted | Without this the operator calls someone to ask why the pump will not start |
| Alarms | Active alarms on this device with priority, and an acknowledge control | Linked to the alarm summary filtered to the device |
| Commands | Start, Stop, Auto, Manual, setpoint entry, reset | Visible or enabled by role; confirmation on Start, Stop, and mode change |
| Diagnostics | Fault code from the drive or starter, seal-leak, thermal, last fault time | A second tab where space is tight |
Layout rules
- Same size, same position of every element, on every faceplate for a device type, and the same zones across device types: header top, status upper left, commands lower right. The operator eye goes to the same place for the same thing.
- Status in text and shape, not color alone. Running, Stopped, Faulted as words; the color is the reinforcement, and it follows the ISA-101 palette used on the displays.
- Commands are buttons that look like buttons, distinct from status indicators, and inactive commands are visibly disabled with the reason available on hover or in a short note.
- Setpoint entry shows the current value, the engineering units, and the allowed range, and rejects out-of-range entry with a message rather than clamping silently.
- A trend button on each process value, opening a pre-configured trend of that value with the related ones: level and speed together, pressure and flow together.
- A single close control in the same corner every time, and no more than two tabs.
Modes and what they mean
Mode confusion is the most common cause of a faceplate command doing nothing. The physical HOA switch at the panel decides whether the controller has authority at all. The controller mode decides whether the automatic sequence or the operator is issuing the command. A local/remote selector at a drive or a packaged system adds a third layer. The faceplate shows all three separately and plainly, so that an operator who presses Start on a pump whose HOA is in OFF sees that the switch is in OFF, rather than a button that appears to do nothing.
| Layer | Where it lives | Faceplate shows |
|---|---|---|
| HOA | Physical switch at the panel | HAND, OFF, or AUTO as read by the controller input; grayed commands when not AUTO |
| Controller mode | Program, per device | AUTO (sequence in control) or MANUAL (operator in control); the toggle command |
| Local or remote | Drive keypad, packaged system panel | Local or remote; grayed commands when local |
| Out of service | Program flag set by the operator | A visible banner; removes the device from rotation and suppresses its alarms by design |
Security and confirmation
Faceplate commands are permitted by user role. A viewer sees status and no commands. An operator sees and may issue operating commands. A supervisor may change setpoints outside the operator range and reset latched faults. An engineer may change tuning and configuration. The roles come from the SCADA security model, and the faceplate simply hides or disables what the current user may not do. Commands with consequences, a start, a stop, a mode change, a setpoint change beyond a threshold, ask for confirmation, and the confirmation dialog names the device and the action so that a misdirected click is caught. Every command is logged with the user, the time, and the device.
Building from a standard
- 1
Define the controller block first
The pump control block in the PLC owns the logic and publishes a status structure. The faceplate is a view of that structure. If the block does not expose a value, the faceplate cannot show it, and the answer is to add it to the block, never to compute it in the HMI.
- 2
Design one faceplate per block type
Pump, valve, analog loop, analyzer, sequence. Lay it out with the rules above and review it with operators before it is instantiated.
- 3
Instantiate by tag
Each device is an instance of the faceplate bound to its block by a tag prefix or a structure reference. No per-device edits.
- 4
Test one, then all
Test the faceplate fully on one device, including every command in every mode and every role. Then spot-check the instances for binding errors.
- 5
Version it with the block
A change to the block that adds a status member is a change to the faceplate. Keep the two in step and record the version on both.
Frequently asked questions
- Should the faceplate contain any logic?
- No. The controller decides whether a command is allowed and what happens; the faceplate sends the request and shows the result. Logic in the HMI diverges from the controller over time, is invisible from the panel, and does not run when the HMI is down.
- How much should be on the faceplate versus the display?
- The display shows what the operator needs to see to know the state of the process without opening anything. The faceplate holds everything about one device. If operators are opening faceplates just to check a value, that value belongs on the display; if the display is crowded with per-device detail, it belongs on the faceplate.
- Can vendors supply faceplates?
- Most SCADA platforms and many integrators supply library objects with matching controller blocks and faceplates, and they are a good starting point. Adopt one library per site rather than mixing, and adjust the layout to the site standard once, before instantiating.
- What about a device with no controller block, like a packaged system?
- Build a faceplate against the status the package exposes over its network interface, and keep the mode layers honest: if the package is in local, the faceplate says so and disables commands. A faceplate that pretends to control a package that is not listening trains operators to distrust all of them.
Related topics
- ISA-101: Human Machine InterfacesWhat the ISA-101 standard for human machine interfaces covers, its lifecycle from philosophy to maintenance, the display hierarchy, and what adopting it changes on a project.
- High Performance HMI DesignGrey backgrounds, reserved color, and displays designed to make abnormal conditions obvious rather than to look impressive in a demo.
- Function Block DiagramThe graphical data-flow language of IEC 61131-3: how blocks, pins, and wires work, execution order, where FBD beats ladder and structured text, building reusable equipment blocks, and the habits that keep a diagram readable.
- Hand-Off-Auto SelectorsWhat each position of an HOA selector does, how it is wired into the starter circuit, which protections must survive Hand, what the controller should see, and the mistakes that let a pump run with nobody watching.
- Interlocks and PermissivesA permissive lets you start. An interlock stops you. Confusing the two produces equipment that either will not run or will not protect itself.
- Alarm PriorityHow to assign alarm priorities that operators trust: a consequence-and-time matrix, three or four levels, the target distribution from ISA-18.2 and EEMUA 191, and the mistakes that make every alarm high.