The short answer
Historian Compression
Historian compression reduces stored data by keeping only the points needed to reconstruct the signal within a tolerance: an exception deadband at the collector drops values that have not moved, and a swinging door algorithm at the archive drops values that lie on a straight line between kept points, within a compression deviation. Both are lossy by design, the loss is the deviation setting, and a deviation set wider than the process detail turns a trend into a sequence of straight segments. Modern storage makes aggressive compression unnecessary for most utilities; the settings are chosen per tag from what the trend must show, and checked by comparing raw and stored data on the tags that matter.
Key points
- Two stages: exception at the collector, compression at the archive. Each has a deviation setting.
- Swinging door keeps the points that a straight line cannot predict within the deviation.
- The deviation is the loss. Set it below the detail the trend must show.
- Storage is cheap now. Aggressive compression solves a problem most utilities no longer have.
- Verify by trending raw against stored on a critical tag. If they differ visibly, the setting is wrong.
Why compress at all
Historians were designed when disk was expensive and a plant had tens of thousands of tags. Storing every sample of every tag was impossible; storing only what was needed to redraw the signal was the solution, and the algorithms that do it are still in every historian. Disk is now cheap and a utility has thousands of tags, not hundreds of thousands, so the pressure is gone. What remains is that compression, well set, produces a cleaner archive and faster queries, and, badly set, produces a record that has lost the thing someone will later need to see. The settings deserve the same attention as the collection rates.
Exception and compression
| Stage | Where | Rule | Setting | What it removes |
|---|---|---|---|---|
| Exception | At the collector, before sending | Send a value only if it differs from the last sent value by more than the exception deviation, or if the maximum time has passed | Exception deviation and maximum interval | Repeats of the same value; noise within the deviation |
| Compression | At the archive, before storing | Store a value only if a straight line from the last stored point cannot pass within the compression deviation of every value since; the swinging door | Compression deviation and maximum interval | Points that lie on a straight trend within the deviation |
The two work together: exception thins the stream from the source, compression thins it again at the archive. Typical guidance sets the exception deviation to a little more than the measurement noise and the compression deviation to about twice the exception deviation. Both have a maximum interval, so that a perfectly steady value still stores a point periodically.
Swinging door
The compression algorithm most historians use is swinging door trending. When a value arrives, the archive asks whether a single straight line could be drawn from the last stored point through all the values received since, staying within the compression deviation of each. If yes, the newest value is held as a candidate and nothing is stored. If no, the previous candidate is stored as a new anchor and the line starts again from it. The result is a set of stored points from which the original signal can be reconstructed by straight-line interpolation within the deviation, and the count of stored points depends on how often the signal changes direction, not on how often it was sampled.
Settings by tag
| Tag | Exception | Compression | Note |
|---|---|---|---|
| Control loop PV, during tuning or analysis | Small, at the noise level | Zero, or off | The dynamics are the point |
| Level | A fraction of an inch | An inch or so | The cycles survive; the ripple does not |
| Compliance analyzer value | Small | Zero or very small | The record should be the measurement, not a reconstruction |
| Flow rate | A percent of range | Two percent | Totals come from a separate totalizer tag, not from integrating compressed rate |
| Motor current | A percent of range | Two percent | Wear trends are slow |
| Digital states | None | None | Every transition is stored |
| Setpoints | None | None | Every change is stored |
| Totalizers | None | None | A total is a fact at a time; never compress |
The staircase and the flat line
Two symptoms say the settings are wrong. A trend that looks like a staircase, flat segments joined by steps, has an exception deviation wider than the movement of the value; the historian only stored the value when it had moved a whole step. A trend that is a straight line across hours while the value was moving has a compression deviation wider than the movement. Both are found by trending the live value from SCADA beside the stored value from the historian on the same chart. The live one is the truth; the stored one should match it as closely as the deviation allows.
Lossless and modern alternatives
Some historians and time-series databases now offer lossless compression, encoding the raw samples compactly without discarding any, at storage costs that are acceptable for utility tag counts. Where the platform offers it, a utility can store every sample of its critical tags losslessly and use deviation compression only on the bulk. The choice is per tag, and the compliance and the control analysis tags are the first candidates for lossless.
Frequently asked questions
- What compression deviation should I use?
- For most analog tags, about twice the exception deviation, which is itself a little above the noise: for a level with an inch of noise, an exception of one and a half inches and a compression of three. Then trend live against stored and adjust. For anything analyzed later, tighter, down to zero.
- Does compression affect totals and averages?
- Averages and totals computed from compressed data are approximations within the deviation, which is usually fine for a daily average level and not fine for a billing or a compliance total. Totals come from a totalizer tag in the controller stored uncompressed, never from integrating a compressed rate.
- Can I turn compression off?
- Yes, for a tag or for the archive, and with modern storage many utilities do for their critical tags. The archive grows faster and queries return more points; the platform documentation gives the storage estimate. A middle path is a small deviation, which removes the noise and little else.
- Why does the historian trend not match the SCADA trend?
- The historian is showing compressed data and the SCADA buffer is showing raw samples, or the two are drawn at different sampling. A visible difference on a value that matters means the deviation is too wide; a small smoothing on a noisy value is expected.
Related topics
- Historian Data CollectionDeciding what the historian stores and how often: polled versus exception collection, the deadband per tag, rates for control loops, levels, totals, and compliance values, timestamps at the source, quality codes, calculated tags, and the tag list review that keeps a historian from filling with noise and missing what matters.
- Historian ArchitectureHow process history is collected, stored, and served: the collector, the archive, and the client layers, where the historian sits relative to SCADA and the DMZ, single-server and tiered designs for a utility, the store-and-forward buffer that survives outages, and the sizing that decides how many years fit on a disk.
- Trends on the HMITrend displays that answer questions: embedded sparklines on process displays, pre-configured trend groups, the axes and time spans that make a trend readable, and the difference between a trend for operating and a trend for investigating.
- Deadband and HysteresisWhy a single setpoint chatters, how a deadband turns it into a start point and a stop point, how wide to make it, and where deadbands belong in alarms, level control, and controller outputs.
- Filtering Analog InputsHow to damp a noisy analog input in the controller without hiding a real process change: the first-order filter, the moving average, the median, where each belongs, and what never to filter.
- TrendingUsing historian trends to understand a process and diagnose a problem: pens that belong together, scaling and time ranges, raw versus averaged data and what compression hides, overlays and cursors, event markers, and the patterns that point at each cause.
Direct contact
Have a controls question?
Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.