Skip to main content
Call Eric:863-698-8266
CURRYCONTROLS.COMControls & Automation Knowledge Hub
ReferenceAlarmsSCADAISADesign

Alarm Floods

What an alarm flood is, why it happens at exactly the wrong moment, the ISA-18.2 rate targets, and the design measures that keep a power failure or a communication loss from burying the one alarm that matters.

10 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Alarm Floods

An alarm flood is a period when alarms arrive faster than an operator can read them. ISA-18.2 defines it as more than ten alarms in ten minutes for one operator and sets a target of under one percent of time in flood. Floods follow upsets such as a power failure or a communication loss, when a single cause triggers hundreds of consequential alarms. They are prevented by state-based suppression, first-out logic, quality gating, and rationalization of the alarms that make up the flood.

Key points

  • Ten alarms in ten minutes per operator is the ISA-18.2 flood threshold. Target under one percent of time in flood.
  • Floods are caused by one event with many symptoms. Suppress the symptoms, alarm the event.
  • A communication loss must produce one alarm, not one per tag.
  • Loss of power at a site is one alarm. The forty things that stopped are consequences.
  • Analyze floods from the history. The same few causes account for most of them.

What a flood is

A flood is a burst of alarms that exceeds what an operator can process. ISA-18.2 draws the line at more than ten alarms in any ten-minute period for a single operator position, and sets a performance target that the system be in flood less than one percent of the time. Its companion metric is the average rate: about one alarm per ten minutes is very likely acceptable, two per ten minutes is the most that is manageable, and more than that in steady operation means the alarm system is not doing its job.

The problem with a flood is not the count. It is that the one alarm that matters is somewhere in the two hundred that arrived with it. Every major incident investigation that touches alarm systems finds the same thing: the alarm that would have told the operator what was happening was on the screen, and the operator did not see it because it was one line among many.

Why floods happen

Floods are caused by one event with many symptoms. The alarm system was configured tag by tag, so each symptom got its own alarm, and when the event occurs they all fire together.

Triggering eventWhat floodsThe alarm that should exist
Communication loss to a remote siteEvery tag at the site goes bad quality, and each may alarm; every derived alarm at the site firesOne alarm: site communication failed
Loss of power at a plant or siteEvery motor stops, every drive faults, every analyzer alarms, every level starts movingOne alarm: site power lost, with the consequential alarms suppressed while it stands
SCADA server failoverEvery tag re-initializes; alarms that depend on quality or on a stale value fireOne event: failover occurred, and no alarms from initialization
A pump tripsPump fault, pump failed to run, low flow, low pressure, high level downstream, low level upstream, and every alarm that depends on flowThe pump fault, and the process alarms the operator must still act on, with a short delay so the first-out is clear
A planned shutdown or maintenanceEvery alarm that expects the equipment to be runningNone; the alarms are suppressed by the equipment state or shelved by the operator
Instrument failure on a shared signalEvery alarm derived from the measurement fires and clears as the signal swingsOne alarm: signal failed, with derived alarms inhibited on bad quality

Design measures

State-based suppression
An alarm is inhibited when the process state makes it expected. A low flow alarm on a pump that is commanded off is suppressed by the pump state. A low pressure alarm on a system in maintenance mode is suppressed by the mode. This is designed suppression, documented in rationalization, not an operator hiding an alarm.
Quality gating
An alarm derived from a measurement is inhibited when the measurement has bad quality, and the bad quality itself is alarmed once. A tag that goes bad on communication loss must not also generate high, low, and rate alarms on whatever value it froze at.
Consequential alarm suppression
When a defined parent event is active, such as site power lost, its defined child alarms are suppressed and shown in a separate list. The operator sees the cause and can drill into the consequences if they want them.
First-out
When several related alarms occur within a short window, the first is flagged as the initiating event. Common on motor and drive protection, where the first trip explains the rest.
Delays and deadbands
A few seconds of on-delay on alarms that respond to the same disturbance lets the initiating alarm arrive first and prevents transient alarms during a switchover.
Communication alarm design
One alarm per communication path, generated by the driver or the poll status, with all tag-level alarms on that path inhibited on loss. This is the single most effective flood prevention at a utility with many remote sites.
Eclipsing
A high-high alarm eclipses the high alarm on the same tag, so the operator sees one line, not two.

Analyzing floods

The alarm history identifies floods after the fact, and the analysis is straightforward: find every ten-minute window with more than ten alarms, list the alarms in each, and find the initiating event. At most sites a handful of event types account for nearly all floods, and each has a design fix from the list above. Commercial alarm management software does this analysis automatically; a spreadsheet on the history export does it well enough.

  1. 1

    Export the alarm history

    Three to six months, with tag, priority, timestamp, and state.

  2. 2

    Find the flood windows

    Rolling ten-minute counts per operator position. Mark every window over ten.

  3. 3

    Group by cause

    For each flood, identify the first alarm and the event behind it. Floods cluster into a few causes.

  4. 4

    Count the contributors

    Within each cause, which alarms appear every time? Those are the consequential alarms to suppress or remove.

  5. 5

    Fix the top cause first

    Implement the suppression or the single parent alarm, then re-measure. Repeat.

During a flood

Design reduces floods; it does not eliminate them. The alarm summary should let the operator filter by priority so that in a flood they see only high alarms, and it should offer a view grouped by area or by parent event. Operators are trained that in a flood the first action is to filter, the second is to find the cause, and acknowledging everything to clear the screen is never the answer, because it discards the information the flood contains.

Frequently asked questions

Is ten alarms in ten minutes really the limit?
It is the ISA-18.2 definition of a flood, derived from what an operator can reasonably read and understand. Operators can physically acknowledge far more, which is exactly the problem: acknowledgment rate is not comprehension rate. The number is per operator position, so a control room with two operators has two thresholds.
Our SCADA system generates an alarm for every tag when a site goes offline. How do we fix it?
Generate a single communication alarm from the poll status of that site and configure the tag alarms to be inhibited on bad quality. Most SCADA platforms have both features; some need the inhibit built in the alarm expression. It is one afternoon of configuration per platform and removes the most common flood at a utility.
Is suppression the same as shelving?
No. Suppression is designed into the system based on process state and documented in rationalization. Shelving is an operator temporarily removing a nuisance alarm from view for a set time, after which it returns. Both are legitimate and both are visible; disabling an alarm silently is neither.
What about a flood of alarms from a real emergency?
A real emergency produces real alarms, and some floods are unavoidable. The design goal is that the operator can still find the cause: high priority filtering, first-out flags, and consequential suppression all work during a real event as well as a nuisance one. The rationalized alarm list also matters here: if only five percent of alarms are high, filtering to high shows a short list.

Direct contact

Have a controls question?

Reach Eric Sullivan directly about anything on this site, a controls or automation topic, or one of his personal projects.