The short answer
Magnetic Flowmeters
A magnetic flowmeter measures flow by applying a magnetic field across a pipe and measuring the voltage the moving conductive liquid induces, following Faraday's law of induction. It has no moving parts and no obstruction in the bore, so it handles wastewater and slurries well. It requires an electrically conductive liquid, a completely full pipe, and correct grounding to the fluid.
Key points
- Induced voltage is proportional to velocity, so the meter reads velocity and computes flow from bore area.
- The liquid must be conductive, typically above roughly 5 microsiemens per centimeter.
- The pipe must be full. A partially full pipe produces a wrong reading, not an obvious failure.
- Grounding rings or grounding electrodes give the measurement its reference.
- No obstruction and no moving parts make it well suited to raw wastewater and sludge.
The principle
Coils on the meter body generate a magnetic field across the bore. As a conductive liquid moves through that field, it behaves like a conductor moving through a magnetic field and a voltage is induced perpendicular to both. Electrodes in contact with the liquid pick up that voltage, which is directly proportional to average velocity.
E = k × B × D × v
- E — induced voltage measured at the electrodes
- k — a constant for the meter
- B — magnetic field strength
- D — internal pipe diameter
- v — average fluid velocity
Because B, D, and k are fixed for a given meter, the measured voltage is a direct function of velocity. Volumetric flow follows from velocity multiplied by the cross-sectional area of the bore, which is why the configured pipe size in the transmitter must match the meter body exactly.
What it needs to work
- Conductive liquid
- Water, wastewater, slurries, and most process liquids qualify. Typical minimum conductivity is around 5 microsiemens per centimeter, with some meters going lower. Hydrocarbons, oils, and deionized water generally do not work.
- Full pipe
- A partially full pipe exposes an electrode to air and produces an erroneous reading. Mount in a location that stays full: a vertical run with upward flow is ideal, and a low point in a horizontal run is acceptable.
- Straight run
- Typically five pipe diameters upstream and two or three downstream, though many modern meters need less. Elbows, valves, and pumps immediately upstream distort the velocity profile.
- Grounding to the fluid
- The measurement is a small voltage referenced to the liquid. Grounding rings, grounding electrodes, or a metallic grounded pipe on both sides establish that reference.
Installation that works
- 01Choose a location that stays full at all flows, ideally a vertical run flowing upward.
- 02Respect the manufacturer straight-run requirement upstream and downstream.
- 03Do not install immediately downstream of a control valve or a pump discharge if it can be avoided.
- 04Install grounding rings on both ends unless the meter is between grounded metallic pipe and the manufacturer permits it.
- 05Bond the grounding rings to the meter body ground and to a good ground per the manufacturer instructions.
- 06Verify the flow direction arrow matches the actual flow.
- 07Confirm the configured pipe size and units in the transmitter match the physical meter.
- 08Keep the signal cable away from drive output conductors, and use the manufacturer cable where specified.
Reading problems and where to look
| Symptom | Common cause | Check |
|---|---|---|
| Erratic or noisy reading | Grounding not established to the fluid | Grounding rings present and bonded |
| Reads low consistently | Partially full pipe, or wrong configured pipe size | Installation elevation and transmitter configuration |
| Reads flow at zero flow | Electrode coating, or a grounding problem | Inspect electrodes; verify at true no-flow with a closed valve |
| Drifts over months | Electrode fouling from grease or scale | Clean electrodes; consider a meter with cleaning electrodes |
| Reading jumps when a drive runs | Induced noise on the signal cable | Cable routing and separation from drive output conductors |
| Totalizer disagrees with plant balance | Low flow cutoff set too high or too low | Compare configured cutoff against actual minimum flow |
Choosing a size
Meters are sized on velocity, not on pipe size. The usual target is roughly 3 to 10 feet per second at normal flow. Too slow and the induced voltage is small relative to noise, which shows up as poor accuracy at low flow. Too fast accelerates liner and electrode wear, particularly with grit.
This is why a meter is often one size smaller than the pipe it sits in. A 12-inch line running well below design flow may need an 8-inch meter with reducers to keep velocity in a usable range. Check the actual operating flow range rather than the pipe size on the drawing.
Frequently asked questions
- Can a magnetic flowmeter measure a partially full pipe?
- A conventional one cannot; it will read low and give no obvious indication. Purpose-built partially-filled meters exist with additional electrodes for level, but for a standard mag meter, a full pipe is a requirement.
- Do magnetic flowmeters work on drinking water?
- Yes. Potable water is conductive enough. Verify the liner and electrode materials are approved for potable contact for your jurisdiction.
- Why does my mag meter read flow when the pump is off?
- Either there is genuine flow, such as backflow through a check valve, or the measurement has no proper ground reference. Close an isolation valve to establish true zero flow and observe. If it still reads, look at grounding and electrode condition.
- How often should a mag meter be calibrated?
- The electromagnetic measurement itself is stable and does not drift the way a mechanical meter does. Most utilities verify annually and clean electrodes as needed. Where the meter is used for billing or regulatory reporting, follow the requirement that applies to you.
Related topics
- Flowmeter InstallationThe installation rules that decide whether a flowmeter reads correctly: straight run by meter type, keeping the pipe full, orientation, velocity range, grounding for magnetic meters, isolation and access, and the commissioning checks that prove the meter.
- Flow TroubleshootingA method for a flow reading that is wrong, noisy, zero, or disputed: establish the truth with an independent check, separate installation from configuration from signal chain, then the specific checks for magnetic, ultrasonic, and DP meters.
- Ground Loops in InstrumentationTwo grounds at different potentials, one signal circuit between them, and a reading that will not sit still. How to find it and how to prevent it.
- How to Troubleshoot a FlowmeterWork a flowmeter that reads wrong, reads zero, or reads with the pipe still: confirm the pipe is full and the flow is real, check the installation against the meter requirements, and compare against an independent measurement before adjusting anything.
- Ultrasonic FlowmetersTransit-time and Doppler ultrasonic flow measurement: how each works, which liquids each suits, clamp-on versus wetted transducers, the pipe data the meter needs, the accuracy to expect, and the installation details that decide whether to trust the reading.
- Differential Pressure Flow MeasurementOrifice plates, venturis, and flow nozzles: the square-root relationship, why turndown is limited, where the square root is taken, impulse line rules, and when a DP element is still the right choice against a mag meter.