Magnetic Flowmeters

Faraday's law applied to a pipe: how a mag meter works, the conductivity and full-pipe requirements, and why grounding decides whether it reads.

8 min readUpdated Aug 1, 2026Published Apr 16, 2026By Eric Sullivan

The short answer

Magnetic Flowmeters

A magnetic flowmeter measures flow by applying a magnetic field across a pipe and measuring the voltage the moving conductive liquid induces, following Faraday's law of induction. It has no moving parts and no obstruction in the bore, so it handles wastewater and slurries well. It requires an electrically conductive liquid, a completely full pipe, and correct grounding to the fluid.

Key points

  • Induced voltage is proportional to velocity, so the meter reads velocity and computes flow from bore area.
  • The liquid must be conductive, typically above roughly 5 microsiemens per centimeter.
  • The pipe must be full. A partially full pipe produces a wrong reading, not an obvious failure.
  • Grounding rings or grounding electrodes give the measurement its reference.
  • No obstruction and no moving parts make it well suited to raw wastewater and sludge.

The principle

Coils on the meter body generate a magnetic field across the bore. As a conductive liquid moves through that field, it behaves like a conductor moving through a magnetic field and a voltage is induced perpendicular to both. Electrodes in contact with the liquid pick up that voltage, which is directly proportional to average velocity.

E = k × B × D × v

  • E — induced voltage measured at the electrodes
  • k — a constant for the meter
  • B — magnetic field strength
  • D — internal pipe diameter
  • v — average fluid velocity

Because B, D, and k are fixed for a given meter, the measured voltage is a direct function of velocity. Volumetric flow follows from velocity multiplied by the cross-sectional area of the bore, which is why the configured pipe size in the transmitter must match the meter body exactly.

What it needs to work

Conductive liquid
Water, wastewater, slurries, and most process liquids qualify. Typical minimum conductivity is around 5 microsiemens per centimeter, with some meters going lower. Hydrocarbons, oils, and deionized water generally do not work.
Full pipe
A partially full pipe exposes an electrode to air and produces an erroneous reading. Mount in a location that stays full: a vertical run with upward flow is ideal, and a low point in a horizontal run is acceptable.
Straight run
Typically five pipe diameters upstream and two or three downstream, though many modern meters need less. Elbows, valves, and pumps immediately upstream distort the velocity profile.
Grounding to the fluid
The measurement is a small voltage referenced to the liquid. Grounding rings, grounding electrodes, or a metallic grounded pipe on both sides establish that reference.

Installation that works

  1. 01Choose a location that stays full at all flows, ideally a vertical run flowing upward.
  2. 02Respect the manufacturer straight-run requirement upstream and downstream.
  3. 03Do not install immediately downstream of a control valve or a pump discharge if it can be avoided.
  4. 04Install grounding rings on both ends unless the meter is between grounded metallic pipe and the manufacturer permits it.
  5. 05Bond the grounding rings to the meter body ground and to a good ground per the manufacturer instructions.
  6. 06Verify the flow direction arrow matches the actual flow.
  7. 07Confirm the configured pipe size and units in the transmitter match the physical meter.
  8. 08Keep the signal cable away from drive output conductors, and use the manufacturer cable where specified.

Reading problems and where to look

SymptomCommon causeCheck
Erratic or noisy readingGrounding not established to the fluidGrounding rings present and bonded
Reads low consistentlyPartially full pipe, or wrong configured pipe sizeInstallation elevation and transmitter configuration
Reads flow at zero flowElectrode coating, or a grounding problemInspect electrodes; verify at true no-flow with a closed valve
Drifts over monthsElectrode fouling from grease or scaleClean electrodes; consider a meter with cleaning electrodes
Reading jumps when a drive runsInduced noise on the signal cableCable routing and separation from drive output conductors
Totalizer disagrees with plant balanceLow flow cutoff set too high or too lowCompare configured cutoff against actual minimum flow

Choosing a size

Meters are sized on velocity, not on pipe size. The usual target is roughly 3 to 10 feet per second at normal flow. Too slow and the induced voltage is small relative to noise, which shows up as poor accuracy at low flow. Too fast accelerates liner and electrode wear, particularly with grit.

This is why a meter is often one size smaller than the pipe it sits in. A 12-inch line running well below design flow may need an 8-inch meter with reducers to keep velocity in a usable range. Check the actual operating flow range rather than the pipe size on the drawing.

Frequently asked questions

Can a magnetic flowmeter measure a partially full pipe?
A conventional one cannot; it will read low and give no obvious indication. Purpose-built partially-filled meters exist with additional electrodes for level, but for a standard mag meter, a full pipe is a requirement.
Do magnetic flowmeters work on drinking water?
Yes. Potable water is conductive enough. Verify the liner and electrode materials are approved for potable contact for your jurisdiction.
Why does my mag meter read flow when the pump is off?
Either there is genuine flow, such as backflow through a check valve, or the measurement has no proper ground reference. Close an isolation valve to establish true zero flow and observe. If it still reads, look at grounding and electrode condition.
How often should a mag meter be calibrated?
The electromagnetic measurement itself is stable and does not drift the way a mechanical meter does. Most utilities verify annually and clean electrodes as needed. Where the meter is used for billing or regulatory reporting, follow the requirement that applies to you.