What each position of an HOA selector does, how it is wired into the starter circuit, which protections must survive Hand, what the controller should see, and the mistakes that let a pump run with nobody watching.

7 min readUpdated Sep 5, 2026Published Sep 5, 2026By Eric Sullivan

The short answer

Hand-Off-Auto Selectors

A Hand-Off-Auto selector decides who commands a pump. In Hand the operator runs it from the panel, bypassing the controller’s logic; in Off it cannot run; in Auto the controller runs it. The selector sits in the starter control circuit so that its authority is electrical, not software. Overloads and safety interlocks stay in the circuit in every position, the controller is told which position the selector is in, and Hand is for a person standing at the panel, not a way to leave a pump running unattended.

Key points

  • The selector is in the starter coil circuit, so Off is Off whatever the controller does.
  • Hand bypasses the controller’s start logic and nothing else: overloads, motor protection, and safety interlocks remain.
  • The controller gets an input for Auto, and preferably for Hand, so it knows what it is and is not controlling.
  • A pump running in Hand with no level control is an overflow or a dry run waiting to happen; alarm it and time it.
  • An HMI Hand is a software mode and is not the same thing; the physical selector still governs.

The three positions

Hand
The selector connects the starter coil, through the protective devices, to control power. The pump runs as long as the selector is in Hand. The controller’s start command is out of the circuit.
Off
The coil circuit is open. Nothing starts the pump, from the panel or from the controller. Off is not a lockout, and it is not a substitute for one.
Auto
The coil circuit runs through the controller’s output relay. The pump runs when the controller commands it, through whatever logic, level control, alternation, and interlocks the program has.

The circuit

The selector sits in the 120 VAC control circuit of the starter or, for a drive, in the run command circuit. From control power, the circuit passes through the safety and protective devices that apply in every mode, then through the selector, and from the Auto contact through the controller’s output relay, to the coil. The overload relay contact, the motor protection, and any hardwired interlock that protects people or the pump itself are upstream of the selector, so that Hand cannot defeat them. The level float that starts the pump in a lift station is, by contrast, a control device, and Hand bypasses it on purpose.

What the controller should see

A controller that does not know a pump is in Hand reports it as failed to start when it is off, or as running unexpectedly when it is on, and its alternation and its runtime accounting go wrong. The selector should have a spare contact that closes in Auto, wired to a controller input, and preferably a second contact for Hand. With those, the program knows whether its command is in charge, can alarm when a pump has been out of Auto for longer than a set time, can accumulate runtime in Hand from the run feedback, and can skip a pump that is not available to it in the alternation sequence.

SignalSourceUsed for
In AutoSelector contactWhether the controller is in control; alternation availability; not-in-auto alarm
In HandSelector contactDistinguishing Hand from Off; Hand runtime alarm
RunningStarter auxiliary contact or drive run statusRun confirmation, fail-to-start detection, runtime hours in every mode
Overload trippedOverload relay auxiliary contactFault alarm; taking the pump out of the alternation
Inputs from the pump circuit

Hand is not unattended operation

A pump in Hand runs until someone turns the selector, whatever the level does. In a lift station that is a dry well and a burned pump if the level falls, or, if Hand was used to force a pump on during a high level and then forgotten, nothing at all until the next high level, when the pump is already on and the second one is the only reserve. The program should alarm when a pump has been in Hand for more than a few minutes, and the operating procedure should say that Hand is for a person at the panel. Some designs add a timed Hand, which returns the selector circuit to Auto after a period, at the cost of the simplicity that makes the selector trustworthy.

HMI modes and the physical selector

Modern systems add a software manual mode on the HMI: the operator commands the pump from the screen, through the controller, bypassing the automatic logic but not the controller. That is useful and it is a different thing. The physical selector in Auto is what lets the HMI command work at all; the physical selector in Hand or Off overrides the HMI entirely. The narrative names both modes and says which governs, and the HMI shows the physical selector position so that an operator is not commanding a pump that the panel has taken away from them.

Two-position and drive-based variants

Some panels use a two-position Auto-Off selector with a separate momentary Hand pushbutton, so that Hand cannot be left on. Drives often carry their own Hand-Off-Auto on the keypad, which selects whether the drive takes its run and speed commands from the keypad or from the controller, and it is a second selector that the program must also know about, because a drive in keypad mode ignores the panel selector.

Frequently asked questions

Should the PLC be able to start a pump in Hand?
No. Hand is the operator’s mode and the controller is out of the coil circuit. The controller sees the run feedback and, ideally, the selector position, and it accounts for the pump but does not command it.
What stays active in Hand?
Everything that protects the motor or a person: overload, motor thermal protection, seal failure trip if it is configured as a trip, and safety interlocks. What Hand bypasses is the controller’s decision to run, including level control and alternation.
Do I need a PLC input for the selector position?
Yes, at least for Auto. Without it the controller cannot tell a pump that failed to start from one that is in Off, cannot alarm a pump left in Hand, and cannot manage alternation correctly.
Is Off the same as locked out?
No. Off opens the control circuit; the motor circuit is still energized and the selector can be turned by anyone. Lockout is the disconnect, opened and locked, per the site procedure.