The short answer
Enclosure Selection
An enclosure is selected by the environment it will sit in, which fixes the type rating and the material; by what goes inside, which fixes the size through heat and wire bending space; and by who has to work in it, which fixes the mounting and the door. A Type 4X stainless or fiberglass enclosure for a lift station in the weather, a Type 12 painted steel enclosure for a plant control room, and a Type 1 for a clean indoor space are the usual answers, and every one of them is only as good as its conduit entries and its door seal.
Key points
- The type rating describes what the enclosure keeps out; the material describes what it survives. Both are chosen from the site.
- Outdoor and wet well sites are Type 4X; corrosive atmospheres and sunlight push the choice between stainless and fiberglass.
- Size is set by the heat the contents produce and by the wire bending space the code requires at terminals, not by what fits.
- Every conduit entry, cable gland, and door-mounted device must carry the same rating or the enclosure does not.
- Plan the working space in front, the door swing, and how a technician gets to the back of the door.
Type ratings
Enclosure types in North America are defined by NEMA 250 and UL 50, and the number on the label describes the environment the enclosure is built for. The types that appear in controls work are few.
| Type | Environment | Keeps out | Typical use |
|---|---|---|---|
| 1 | Indoor, general purpose | Contact with the contents, falling dirt | Clean electrical rooms |
| 12 | Indoor, industrial | Dust, dripping and splashing non-corrosive liquids | Plant floors and control rooms |
| 3R | Outdoor | Rain, sleet, and snow; not wind-driven dust | Meter and service enclosures, outdoor disconnects |
| 4 | Indoor or outdoor | Windblown dust, rain, splashing and hose-directed water | Washdown areas, outdoor panels |
| 4X | Indoor or outdoor | Everything Type 4 does, plus corrosion | Lift stations, treatment plants, coastal and chemical sites |
| 13 | Indoor | Dust, spraying water, oil, and non-corrosive coolant | Machine tools |
| 7 and 9 | Hazardous locations | Contains an internal explosion, or excludes dust | Classified areas; the UL 698A page |
The rating is a property of the enclosure as tested with its door closed and its knockouts unused. It says nothing about what the installer does to it. A Type 4X enclosure with a general-purpose conduit fitting in the top, a hole drilled for a pilot light without a gasket, or a door held open by a cable, is a Type 1 enclosure with an expensive label.
Material
- Painted carbon steel
- The standard indoor enclosure. Strong, cheap, easy to modify, and it rusts wherever the paint is broken. Fine for Type 1 and Type 12; poor for anything wet or corrosive.
- Stainless steel, 304 and 316
- The standard for Type 4X. Grade 304 resists most plant environments; 316 resists chlorides, which matters near the coast, near hypochlorite, and in wastewater atmospheres with hydrogen sulfide. Heavy, expensive, and it reflects the sun, which helps.
- Fiberglass reinforced polyester
- Type 4X, immune to most chemicals, non-conductive, lighter than steel. Surface chalks and fades in sunlight, gaskets and hardware are the weak points, and it does not shield radio or electrical noise. The usual choice for a chemical feed panel.
- Polycarbonate
- Small Type 4X enclosures for a few components. Clear covers let a display be seen without opening the door. Limited size and limited load on the mounting panel.
- Aluminum
- Light, corrosion resistant in many environments, good for hazardous location housings. Attacked by some chemicals and by galvanic contact with dissimilar metals.
Size
The temptation is to size the enclosure to what fits. Two things set the size instead. The first is heat: every component dissipates power into the box, and the enclosure surface is what carries it out, so the surface area and the ambient decide whether the inside stays within the ratings of the components. The heat calculations page and the enclosure heat load calculator cover it, and a drive in a small box is the usual way to discover it. The second is wire bending space, which NEC Article 312 requires at every terminal, sized by the conductor and by whether the wire enters opposite the terminal or from the side. A panel with the incoming feeder terminated an inch from the wall is a panel the inspector rejects.
Outdoors
- A sun shield or a drip shield over the top and the sunny face. The sun is a heat source that can exceed the contents.
- A condensation heater with a thermostat, so that a cold night after a warm damp day does not leave water on the electronics.
- Conduit entries from below where possible, with rated fittings and drain fittings at the low points, so that water in the conduit does not run into the panel.
- A dead-front or inner door, so that the outer door can be opened for a display without exposing live parts to the weather and to people.
- Stainless or non-metallic hardware, hinges, and latches. Steel hinges on a stainless box are where the rust starts.
- Pedestal or wall mounting at a height that keeps the bottom above flood and snow, with the working space the code requires in front.
Access and working space
NEC 110.26 requires working space in front of equipment that may need examination or adjustment while energized, typically three feet deep and the width of the equipment or thirty inches, whichever is greater, clear to the floor. The door must open fully into that space. Door-mounted devices need the back of the door reachable, which means the door cannot be against a wall when open. Free-standing enclosures need rear access or a design that puts everything at the front. These are drawn on the layout before the enclosure is ordered, because the wall it will hang on is usually not the wall the drawing assumed.
Frequently asked questions
- What is the difference between Type 4 and Type 4X?
- Both keep out windblown dust, rain, and hose-directed water. Type 4X adds corrosion resistance, meaning stainless steel or a non-metallic material. Any wastewater, coastal, or chemical site is 4X.
- Stainless or fiberglass for a lift station?
- Either is Type 4X. Stainless, 316 for chloride and sulfide exposure, is stronger, shields radio noise, and lasts longest in the sun. Fiberglass is lighter, cheaper, and immune to most chemicals, and it chalks in sunlight and needs its gaskets watched. Both are common; the site chemistry and the budget decide.
- How big should the enclosure be?
- Big enough for the heat and the wire bending space, plus twenty percent spare. Run the heat calculation with the drives and supplies in it, check the bending space at the largest terminals against NEC Article 312, and then see what size that is.
- Does a hole for a pushbutton void the rating?
- It does if the device installed in it is not rated for the enclosure type or is not gasketed as the device manufacturer requires. Door-mounted devices for a Type 4X panel are Type 4X devices, installed to their instructions.
Related topics
- Enclosure Heat CalculationsEstimating the temperature inside a control panel from the power its contents dissipate and the surface that carries it out, what to do when the answer is too hot, and why drives change everything.
- Component LayoutArranging a panel so it is safe to work in, cool enough to run, quiet enough for its signals, and possible to modify: power and control separation, heat, wireways, terminals, and the working space rules.
- UL 508A Industrial Control PanelsWhat the listing actually covers, what has to appear on the label, and the requirements that most often cause a panel to fail inspection.
- UL 698AIndustrial control panels for hazardous locations: what UL 698A adds to UL 508A, a panel in a classified area or a safe-area panel with intrinsically safe circuits, barriers and isolators, the control drawing, and where utilities meet classified areas.
- NFPA 70 and the Control PanelThe National Electrical Code inside an industrial control panel: Article 409 and the listing it points to, the short-circuit current rating, overcurrent protection for control circuits, grounding and bonding, working space, and what an inspector asks.
- Short-Circuit Current Rating (SCCR)What a control panel’s short-circuit current rating means, how it is determined under UL 508A, why the NEC requires it on the label, and why the number is usually smaller than people expect.