Voltage Drop Calculator
Voltage drop over a conductor run, by wire size, material, distance, and load, using the circular-mil method. Shows the arithmetic so it can be checked.
Calculated reference results
- Voltage drop
- 13.53V
- Voltage drop
- 2.82%
- Voltage at the load
- 466.5V
- Smallest size meeting the limit
- 8
Within 3.0%
Needs at least 15,516 circular mils
The arithmetic
- K = 12.9 ohm-cmil/ft for copper
- Phase constant = 1.732 (three phase)
- Circular mils for 8 = 16,510
- VD = (12.9 x 1.732 x 40.0 A x 250 ft) / 16,510 = 13.53 V
- %VD = 13.53 V / 480 V x 100 = 2.82%
What this does not account for
- The circular-mil method uses a fixed K and ignores conductor reactance, power factor, and conductor operating temperature. On large conductors and low power factor loads it can understate the real drop; use an impedance-based method where that matters.
- Voltage drop does not determine conductor size on its own. The conductor must also satisfy ampacity, overcurrent protection, terminal temperature ratings, and short-circuit withstand.
How this is calculated
Voltage drop is calculated as VD = (K x phase constant x current x one-way distance) / circular mils, where K is about 12.9 for copper and 21.2 for aluminum, and the phase constant is 2 for single phase or 1.732 for three phase. The NEC does not mandate a limit, but its informational notes reference roughly 3% on a branch circuit and 5% total including the feeder.
Formulas
VD = (K x n x I x L) / CM
- K — 12.9 for copper, 21.2 for aluminum (ohm-cmil/ft)
- n — 2 for single phase, 1.732 for three phase
- I — load current in amperes
- L — one-way circuit length in feet
- CM — conductor area in circular mils
Assumptions and limitations built into this calculator
- Uses the circular-mil K method with K = 12.9 for copper and 21.2 for aluminum, values commonly cited for uncoated conductors at about 75 degrees C.
- Ignores conductor reactance. Results are least accurate on large conductors, long runs, and low power factor loads.
- Assumes a balanced load and a single conductor per phase.
- Distance is one way. The formula accounts for the return path.
Frequently asked questions
- Does the NEC limit voltage drop?
- Not as a requirement in the general branch-circuit and feeder rules. Informational notes reference about 3% on a branch circuit and 5% total including the feeder, and most specifications adopt those figures as requirements. Some specific applications do carry mandatory limits.
- Should I use one-way or round-trip distance?
- One way. The phase constant in the formula accounts for the return path: 2 for single phase, 1.732 for three phase.
- Why does my drop differ from the manufacturer figure?
- The circular-mil method ignores reactance and assumes a fixed conductor temperature. Manufacturer and software calculations typically use conductor impedance from NEC Chapter 9 Table 9 at a stated power factor, which is more accurate on large conductors.