Voltage Drop Calculator

Voltage drop over a conductor run, by wire size, material, distance, and load, using the circular-mil method. Shows the arithmetic so it can be checked.

Inputs

The NEC does not mandate a limit. 3% branch, 5% total is the figure most specifications use.

Calculated reference results

Voltage drop
13.53V
Voltage drop
2.82%

Within 3.0%

Voltage at the load
466.5V
Smallest size meeting the limit
8

Needs at least 15,516 circular mils

The arithmetic

  1. K = 12.9 ohm-cmil/ft for copper
  2. Phase constant = 1.732 (three phase)
  3. Circular mils for 8 = 16,510
  4. VD = (12.9 x 1.732 x 40.0 A x 250 ft) / 16,510 = 13.53 V
  5. %VD = 13.53 V / 480 V x 100 = 2.82%

What this does not account for

  • The circular-mil method uses a fixed K and ignores conductor reactance, power factor, and conductor operating temperature. On large conductors and low power factor loads it can understate the real drop; use an impedance-based method where that matters.
  • Voltage drop does not determine conductor size on its own. The conductor must also satisfy ampacity, overcurrent protection, terminal temperature ratings, and short-circuit withstand.

How this is calculated

Voltage drop is calculated as VD = (K x phase constant x current x one-way distance) / circular mils, where K is about 12.9 for copper and 21.2 for aluminum, and the phase constant is 2 for single phase or 1.732 for three phase. The NEC does not mandate a limit, but its informational notes reference roughly 3% on a branch circuit and 5% total including the feeder.

Formulas

VD = (K x n x I x L) / CM

  • K — 12.9 for copper, 21.2 for aluminum (ohm-cmil/ft)
  • n — 2 for single phase, 1.732 for three phase
  • I — load current in amperes
  • L — one-way circuit length in feet
  • CM — conductor area in circular mils

Assumptions and limitations built into this calculator

  • Uses the circular-mil K method with K = 12.9 for copper and 21.2 for aluminum, values commonly cited for uncoated conductors at about 75 degrees C.
  • Ignores conductor reactance. Results are least accurate on large conductors, long runs, and low power factor loads.
  • Assumes a balanced load and a single conductor per phase.
  • Distance is one way. The formula accounts for the return path.

Frequently asked questions

Does the NEC limit voltage drop?
Not as a requirement in the general branch-circuit and feeder rules. Informational notes reference about 3% on a branch circuit and 5% total including the feeder, and most specifications adopt those figures as requirements. Some specific applications do carry mandatory limits.
Should I use one-way or round-trip distance?
One way. The phase constant in the formula accounts for the return path: 2 for single phase, 1.732 for three phase.
Why does my drop differ from the manufacturer figure?
The circular-mil method ignores reactance and assumes a fixed conductor temperature. Manufacturer and software calculations typically use conductor impedance from NEC Chapter 9 Table 9 at a stated power factor, which is more accurate on large conductors.