Pipe Velocity and Friction Loss

Velocity and Hazen-Williams friction loss for a water pipe, with the head loss over the run and the velocity checked against practical limits.

Inputs

Valves, bends, and tees expressed as an equivalent straight length.

Calculated reference results

Velocity
5.67ft/s
Friction head loss
47.45ft

Over 2,650 equivalent feet

Friction head loss
20.54psi
Loss per 100 ft
1.790ft
Velocity assessment
Above typical design range.

Water mains are commonly designed around 3 to 5 ft/s. Wastewater force mains generally need at least 2 ft/s to scour.

Equivalent length used
2,650ft

2,500 pipe plus 150 fittings

The arithmetic

  1. Velocity = 0.4085 x 500 gpm / 6.00 in squared = 5.67 ft/s
  2. Loss per 100 ft = 10.44 x 100 x 500^1.852 / (140^1.852 x 6.00^4.87) = 1.790 ft
  3. Total = 1.790 x 2,650 / 100 = 47.45 ft

What this does not account for

  • Hazen-Williams applies to water at ordinary temperatures in turbulent flow. It is not valid for viscous fluids, sludge, or gases.
  • The C value falls as pipe ages and tuberculates. Designing a force main on new-pipe C and never revisiting it understates the head years later.
  • Use the actual inside diameter, not the nominal size. The difference is significant on small pipe and the loss varies with diameter to the 4.87 power.
  • Surge and water hammer are separate analyses. A long force main with a fast-closing valve needs one.

How this is calculated

Velocity in feet per second is 0.4085 multiplied by flow in gallons per minute, divided by the inside diameter in inches squared. Hazen-Williams friction loss depends on flow, diameter, and the roughness coefficient C, which is around 130 to 150 for new pipe and falls as pipe ages.

Formulas

V = 0.4085 x Q / d squared

  • V — ft/s
  • Q — gpm
  • d — inside diameter in inches

h_f per 100 ft = 10.44 x 100 x Q^1.852 / (C^1.852 x d^4.87)

  • C — Hazen-Williams roughness coefficient

Assumptions and limitations built into this calculator

  • Water at ordinary temperature in turbulent flow. Not valid for sludge, viscous fluids, or gases.
  • Inside diameter, not nominal pipe size.
  • Fittings are entered by you as an equivalent straight length.

Frequently asked questions

What C value should I use for an existing force main?
Lower than the new-pipe value. If the main matters, measure it: run the pump, record discharge pressure and flow, and back-calculate C from the observed head loss. That number is worth far more than a table.
What velocity does a force main need?
At least about 2 ft/s at some point in each pumping cycle to scour settled solids. This is one of the constraints that argues for longer pump runs and a wider wet well level band.