Control Panels
Motor Branch Circuit Sizing
Conductor, overload, short-circuit protection, and disconnect sizing for a three-phase motor branch circuit, from the code full-load current rather than the nameplate.
Calculated reference results
- Full-load current used
- 14.0A
- Minimum conductor ampacity
- 17.5A
- Inverse time circuit breaker maximum
- 35 A
- Next standard size up
- 35 A
- Minimum disconnect rating
- 16.1A
- Overload device maximum
- 16.88A
Table 430.250, 10 hp at 460 V. Confirm against your own code book.
125% of full-load current, per 430.22
250% of 14.0 A is 35.0 A. Largest standard size not exceeding that is 35 A.
430.52(C)(1) Exception 1 permits the next higher standard size when the calculated value does not correspond to a standard rating.
115% of full-load current, per 430.110
125% of the 13.5 A nameplate, per 430.32
The arithmetic
- Full-load current = 14.0 A (Table 430.250)
- Conductor = 14.0 x 1.25 = 17.5 A minimum ampacity
- Short-circuit device = 14.0 x 250% = 35.0 A, standard size 35 A
- Disconnect = 14.0 x 1.15 = 16.1 A
- Overload = 13.5 A nameplate x 125% = 16.88 A
What this does not account for
- Overload protection is sized from the motor nameplate current. Everything else is sized from the code table value. Mixing the two up is the most common error in motor circuit sizing.
- The Table 430.52 percentages shown are the general values for a squirrel-cage AC motor. Design B energy-efficient motors, wound-rotor motors, direct-current motors, and synchronous motors use different percentages.
- If the motor will not start on the calculated device, 430.52(C)(1) Exception 2 permits specific increases. That is a documented exception, not a free hand to increase the size.
- Conductor ampacity still has to survive ambient temperature correction and the adjustment for conductor count, and cannot exceed the termination temperature rating.
- This covers a single motor on a branch circuit. Feeders serving several motors, and circuits with additional loads, follow different rules in 430 Part IV.
How this is calculated
A motor branch circuit is sized from the full-load current in NEC Table 430.250, not from the motor nameplate. Conductors are sized at 125% of that value, the short-circuit and ground-fault device is sized from the Table 430.52 percentage for the device type, and the disconnect is rated at least 115% of the full-load current. Overload protection is the one element sized from the nameplate.
Formulas
Conductor ampacity = FLC x 1.25
Short-circuit device = FLC x Table 430.52 percentage
Disconnect = FLC x 1.15
Overload = nameplate FLA x 1.15 or 1.25
Assumptions and limitations built into this calculator
- Single continuous-duty three-phase squirrel-cage motor on its own branch circuit.
- Full-load current from Table 430.250 as commonly published. Verify against your adopted edition.
- Does not apply the Design B energy-efficient motor percentages or the wound-rotor, DC, and synchronous motor rows.
- Does not size feeders, tap conductors, or circuits with combined loads.
Frequently asked questions
- Why does the code use a table value instead of the nameplate?
- So that conductors and protective devices are sized consistently and are not undersized when a motor is later replaced with one of the same horsepower but a different nameplate current. Overload protection is the exception and uses the nameplate, because it is protecting that specific motor.
- Can I round the breaker up to the next standard size?
- 430.52(C)(1) Exception 1 permits the next higher standard rating when the calculated value does not correspond to a standard size. Going beyond that requires one of the specific exceptions, and only when the motor will not start.