DC Power Supply Load Budget
Total 24 VDC load from controller, I/O, transmitters, relays, and network gear, with headroom applied and the heat the supply adds to the enclosure.
Calculated reference results
- Steady-state load
- 2.282A
- With 25% headroom
- 2.853A
- Next common catalog size
- 3.8 A
- Delivered power
- 54.8W
- Heat the supply adds to the enclosure
- 7.5W
2,282 mA
Common catalog ratings. Confirm against the products you actually buy.
At 88% efficiency. Add this to the enclosure heat load.
The arithmetic
- Controller and I/O: 900 mA
- Transmitters: 6 x 22 mA = 132 mA
- Relays: 8 x 25 mA = 200 mA
- Network gear: 900 mA
- Other: 150 mA
- Total = 2,282 mA = 2.282 A
- With headroom = 2.282 x 1.25 = 2.853 A
What this does not account for
- This is steady state only. Relay and contactor coils, capacitive input filters, and switch-mode devices all draw far more at the instant they energize, and a supply that is adequate in steady state can drop out of regulation on a simultaneous energization.
- Power supply ratings derate above their reference ambient. Check the derating curve at the temperature inside the enclosure, not at the outdoor ambient.
- Distribute the output through individually protected branches. A single supply feeding twenty devices through one terminal turns a shorted field wire into a dead panel.
- Consider separating controller power from field device power so a field short cannot take down the processor.
How this is calculated
Size a control power supply by totalling the steady-state current of every load at the supply voltage, adding the largest expected simultaneous inrush, applying at least 25% headroom, and then derating for the actual maximum temperature inside the enclosure. Undersized supplies cause intermittent controller resets that are very hard to diagnose.
Formulas
Rating >= total steady-state current x (1 + headroom)
Heat = delivered watts x (1 / efficiency - 1)
Assumptions and limitations built into this calculator
- Loop-powered transmitters are counted at 22 mA each, slightly above full scale, to cover NAMUR fault currents.
- Steady state only. Inrush is not modelled.
- Catalog sizes shown are common ratings and are not specific to any manufacturer.
Frequently asked questions
- How much headroom is enough?
- At least 25% above the calculated steady-state load, and more where spare I/O capacity exists. The step to the next catalog size is usually cheap compared with diagnosing an intermittent brownout later.
- Why 22 mA per transmitter and not 20?
- A transmitter driving a NAMUR fault current draws slightly more than full scale, and some devices draw more still under alarm conditions. Counting 22 mA removes a small systematic underestimate at no cost.