DC Power Supply Load Budget

Total 24 VDC load from controller, I/O, transmitters, relays, and network gear, with headroom applied and the heat the supply adds to the enclosure.

Inputs

Counted at 22 mA each, slightly above full scale, to cover fault currents.

Calculated reference results

Steady-state load
2.282A

2,282 mA

With 25% headroom
2.853A
Next common catalog size
3.8 A

Common catalog ratings. Confirm against the products you actually buy.

Delivered power
54.8W
Heat the supply adds to the enclosure
7.5W

At 88% efficiency. Add this to the enclosure heat load.

The arithmetic

  1. Controller and I/O: 900 mA
  2. Transmitters: 6 x 22 mA = 132 mA
  3. Relays: 8 x 25 mA = 200 mA
  4. Network gear: 900 mA
  5. Other: 150 mA
  6. Total = 2,282 mA = 2.282 A
  7. With headroom = 2.282 x 1.25 = 2.853 A

What this does not account for

  • This is steady state only. Relay and contactor coils, capacitive input filters, and switch-mode devices all draw far more at the instant they energize, and a supply that is adequate in steady state can drop out of regulation on a simultaneous energization.
  • Power supply ratings derate above their reference ambient. Check the derating curve at the temperature inside the enclosure, not at the outdoor ambient.
  • Distribute the output through individually protected branches. A single supply feeding twenty devices through one terminal turns a shorted field wire into a dead panel.
  • Consider separating controller power from field device power so a field short cannot take down the processor.

How this is calculated

Size a control power supply by totalling the steady-state current of every load at the supply voltage, adding the largest expected simultaneous inrush, applying at least 25% headroom, and then derating for the actual maximum temperature inside the enclosure. Undersized supplies cause intermittent controller resets that are very hard to diagnose.

Formulas

Rating >= total steady-state current x (1 + headroom)

Heat = delivered watts x (1 / efficiency - 1)

Assumptions and limitations built into this calculator

  • Loop-powered transmitters are counted at 22 mA each, slightly above full scale, to cover NAMUR fault currents.
  • Steady state only. Inrush is not modelled.
  • Catalog sizes shown are common ratings and are not specific to any manufacturer.

Frequently asked questions

How much headroom is enough?
At least 25% above the calculated steady-state load, and more where spare I/O capacity exists. The step to the next catalog size is usually cheap compared with diagnosing an intermittent brownout later.
Why 22 mA per transmitter and not 20?
A transmitter driving a NAMUR fault current draws slightly more than full scale, and some devices draw more still under alarm conditions. Counting 22 mA removes a small systematic underestimate at no cost.