Conductor Ampacity with Derating

Allowable ampacity after ambient temperature correction and the adjustment for more than three current-carrying conductors, with the small-conductor overcurrent limit applied.

Inputs

The 90 C column is normally used only as a starting point for derating. Terminations are commonly rated 60 C or 75 C.

Per 110.14(C), the final ampacity cannot exceed the value in the column matching the lowest-rated termination.

Neutrals carrying only unbalanced current and equipment grounding conductors are generally not counted.

Calculated reference results

Ampacity after derating
36.4A

40 A base x 0.91 temperature x 1.00 conductor count

Usable ampacity
35.0A

Limited by the 75 C termination column, not by derating

Table 310.16 value used
40 A

copper 10, 90 C column. Confirm this against your own code book.

Ambient correction factor
0.91

at 40 C

Conductor count adjustment
1.00

3 current-carrying conductors

Largest standard overcurrent device
30 A

Capped at 30 A by the 240.4(D) small conductor rule

Against your load
Ampacity is sufficient

24.0 A load against 35.0 A usable

The arithmetic

  1. Base ampacity, Table 310.16, copper 10, 90 C column = 40 A
  2. Ambient correction at 40 C = 0.91
  3. Adjustment for 3 current-carrying conductors = 1.00
  4. 40 x 0.91 x 1.00 = 36.4 A
  5. Termination limit, 75 C column = 35 A
  6. Usable ampacity = lesser of the two = 35.0 A

What this does not account for

  • Starting from the 90 C column is permitted only for derating. The finished ampacity still cannot exceed the column matching the lowest-rated termination, which 110.14(C) requires you to identify from the equipment marking.
  • Continuous loads generally require the conductor and the overcurrent device to be sized at 125% of the continuous load. That is not applied here.
  • Which conductors count as current-carrying depends on the system. Harmonic-rich loads can make a shared neutral a current-carrying conductor.
  • 240.4(D) caps the overcurrent device for copper 10 at 30 A regardless of the calculated ampacity, with limited exceptions.

How this is calculated

Corrected ampacity is the Table 310.16 value for the conductor size and insulation rating, multiplied by the ambient temperature correction factor and by the adjustment factor for the number of current-carrying conductors in the raceway. The result is then limited by the temperature rating of the terminations, and for small conductors by the overcurrent limits in 240.4(D).

Formulas

I_allowable = I_table x F_temperature x F_conductors

  • I_table — Table 310.16 value at the insulation temperature column
  • F_temperature — ambient correction from Table 310.15(B)(1)
  • F_conductors — adjustment from Table 310.15(C)(1)

Assumptions and limitations built into this calculator

  • Uses Table 310.16, which covers not more than three current-carrying conductors in a raceway, cable, or earth at 30 degrees C ambient.
  • Applies the termination temperature limit from 110.14(C) as a ceiling.
  • Does not apply the 125% continuous load factor, motor rules, or any of the ampacity exceptions.
  • Table values are reproduced for convenience and may not match your adopted edition.

Frequently asked questions

Can I use the 90 C column?
You can start derating from it when the conductor is 90 C rated, but the finished ampacity still cannot exceed the column matching the lowest-rated termination in the circuit. Most equipment terminals are rated 60 C or 75 C.
Which conductors count as current-carrying?
Ungrounded conductors always count. Equipment grounding conductors do not. A neutral carrying only the unbalanced current of a multiwire branch circuit generally does not, but a neutral in a system with significant harmonic content does.
Do both correction and adjustment apply at once?
Yes. When the ambient differs from 30 degrees C and there are more than three current-carrying conductors, both factors multiply the table value.