Instrumentation

4-20 mA Scaling Calculator

Convert between milliamps, percent of span, and engineering units for a 4-20 mA loop, in either direction, with NAMUR fault thresholds shown.

Inputs

Calculated reference results

Current
12.0000mA
Engineering value
12.500ft
Percent of span
50.00%
Voltage across a 250 ohm input
3.0000V
Signal status
Within 4-20 mA

The arithmetic

  1. Fraction of span = (12.000 mA - 4) / 16 = 0.50000
  2. EU = 0.50000 x 25.000 + 0.000 = 12.500 ft

What this does not account for

  • A reading below 3.6 mA or above 21 mA is a fault indication under NAMUR NE 43, not a measurement. Logic that scales it into a plausible engineering value will act on bad data.
  • The transmitter calibrated range, the analog card range configuration, and the scaling constants in the program must all describe the same thing. Nearly every scaling problem is a mismatch between those three.
  • This assumes a linear transmitter. Differential pressure flow requires square root extraction, applied exactly once.

How this is calculated

To convert a 4-20 mA signal to engineering units, subtract 4 from the measured current, divide by 16 to get the fraction of span, multiply by the calibrated span, then add the lower range value. To go the other way, take the fraction of span and multiply by 16 before adding 4.

Formulas

EU = ((mA - 4) / 16) x (EU_max - EU_min) + EU_min

mA = ((EU - EU_min) / (EU_max - EU_min)) x 16 + 4

Assumptions and limitations built into this calculator

  • Linear 4-20 mA transmitter with 4 mA at the lower range value and 20 mA at the upper.
  • Does not apply square root extraction.
  • Does not model transmitter or input card accuracy.

Frequently asked questions

What is 12 mA in engineering units?
Exactly the midpoint of the calibrated range. Checking at 12 mA is the fastest way to catch a span error, and it is the check people skip.
Why is the bottom of the range 4 mA and not 0?
So a genuine zero measurement is distinguishable from a broken circuit. At 4 mA the loop is proven intact; 0 mA means something is open.